1. General Instructions
2. Application
The VariTrans P15000H1-KTA standard-signal isolators are used for galvanic
isolation of 0(4) to 20 mA and 0 ... 10 V standard signals.
DIP switches allow selection of calibrated input and output signals.
Fine-adjusting is not required. Signal transmission is linear.
Connection is made using pluggable screw clamp terminals.
NOTICE!
Only trained and qualified personnel should install the VariTrans
P15000H1-KTA standard-signal isolator. Do not connect the device to
power supply before it is professionally installed. Do not change the
measuring range during operation because live parts are exposed
during this process. Be sure to observe the national codes and
regulations for installation and selection of cables and lines.
Be sure to install a two-pole circuit breaker between device and
mains supply.
Take protective measures against electrostatic discharge (ESD) when
switching the ranges.