40
Made in Germany
Operating temp. 10 to +65°C
I
F-P42000D2TRMS-0001-KTA
CD
EF0
12
34
56
7
89AB
25
Test
Out
I +
I +
+
26
15
11
U ~
U 0
19
Power 18 to 30 V DC
Output
Input
20
27
I
I
28
P42000D2TRMS-0001-KTA
No. 0000000
AC/DC-Transmitter
®
VariTrans
Type P42000D2TRMS-0001-KTA
No. 78271/0000000
ES 04
Power
19 + 20
18 to 30 V DC
AC/DC-Transmitter
®
VariTrans
Input - Output/Supply 10 kV ~
Test
Voltage: Output - Supply
4 kV ~
Range Settings
Terminals
= default
Switch Input output
Input
Output
0
~ + -
0
0
0
0
0
0
0
0
0
to
to
to
to
to
to
to
to
to
110 V~
100 V~
12 V~
110 V~
100 V~
12 V~
110 V~
100 V~
12 V~
0
0
0
4
4
4
to
to
to
to
to
to
mA
mA
mA
mA
mA
mA
mA
mA
mA
20
20
20
20
20
20
Test >22
Test >22
Test >22
0
3
6
1
4
7
2
5
8
Switch positions 9 to F: not used!
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
11 15 27 28
P42000D2TRMS-0001-KTA
Conductor cross sections
Max.:
1 x 2.5 mm
2
stranded wire with ferrule
1 x 4 mm
2
solid
2 x 1.5 mm
2
stranded wire with ferrule
2 x 2.5 mm
2
solid
Min.:
1 x 0.5 mm
2
solid or stranded with ferrule
Stripping length of conductors or sleeve length: 8 mm
The AC/DC voltage transmitters of the VariTrans® P 42000 D2 TRMS-
0001-KTA Series must be installed only by qualified and specially trained
personnel authorized by the operating company. Be sure that there is
sufficient spacing or isolation from neighboring devices and protection
against electric shocks! Do not connect the device to power supply before
it is professionally installed.
Caution!
Do not change the measuring range during operation. The ranges are
selected by turning an insulated rotary encoder switch on the device front
using a screw driver.
1.3 VariTrans® P 42000 D2 TRMS-0001-KTA
Rating plate, range selection