VariTrans® P 41000 D1
Specifications (continued)
Isolation
Protection against
electric shock
• Calibrated range selection:
Protective separation according to EN 61140 by
reinforced insulation in accordance with EN 61010-1.
Working voltages with overvoltage category III and
pollution degree 2:
– up to 1100 V across input, output, and power supply
– up to 300 V across output and power supply
• Fixed setting / types P411xxD1 and P41100D1-nnnn
Protective separation according to EN 61140 by
reinforced insulation in accordance with EN 61010-1.
Working voltages with overvoltage category III and
pollution degree 2:
– up to 1800 V across input, output, and power supply
– up to 300 V across output and power supply
For applications with high working voltages, take measures to prevent accidental contact
and make sure that there is sufficient distance or insulation between adjacent devices.
73