VEB-46/VEP-43 Series 3-Way, NPT, Control Ball Valves (1⁄2 to 21⁄2")
2
Installation Guide
© 2016 KMC Controls, Inc.
050-019-51H
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
For additional instructions on wiring, feedback selec-
tor, and actuator/signal range reset (auto-mapping),
see the
MEP-4000/4800 Series Installation Guide
or
(fail-safe)
MEP-4200/4500/4900 Series Installation
Guide
.
More Information
For
non-fail-safe
wiring,
auxiliary switches, feed-
back/direction selectors,
actuator/signal range reset
(auto-mapping), and other
information, see the
MEP-
4000/4800 Series Installa-
tion Guide
.
For models, specifications,
and additional information,
see the
VEB-46/VFB-46
Series Data Sheet
on the
KMC web site.
CL Wiring (MEP-4x52)
For information on assem-
bling a quick-mount “V”
actuator on a valve body, see
the
HPO-5074 Installation
Guide
.
For
fail-safe
wiring,
auxiliary switches, feed-
back/direction selectors,
actuator/signal range
reset (auto-mapping), and
other information, see the
MEP-4200/4500/4900 Series
Installation Guide
.
Wiring
NOTE: The installed actuator model is indicated
by the last two digits of the VEB valve
model number (e.g., VEB-46xxxx
CK
has an MEP-4002V actuator) and the
last three digits of the older VEP valve
model number (e.g., VEP-43xxx
745
has an
MEP-4002 actuator).
For wiring and other
information about tri-state and other
actuators no longer sold mounted on
these valves, see the respective actuator’s
installation guide on the KMC web site.
CK/745 Wiring (MEP-4002)
Power
Supply
~
–
–
+
Control Signal:
0–10 or
2–10 VDC
–
+
Feedback Output:
1–5 or 2–10 VDC
(with 2–10 VDC Input)
or 0–5 or 0–10 VDC
(with 0–10 VDC Input)
–
–
–
~/+
+
Control Signal
2–10 VDC
or 0–10 VDC
Power Supply
24 VAC/VDC
OUT (Green)
INPUT (White)
T
COM (Blac
k)
~24
V (Red)
+
Feedback Output
1–5 or 2–10 VDC
or
0–5 or 0–10 VDC