Installation Guide

3/4" & 1" 3-Way Diverting Electronic Control Valves

VEP–3420, 3421 Series

NOTE: Models

 do not include

HMO–5026/5027 MPT unions as
shown. Order separately.

DIMENSION REFERENCE

A

B

C

D

3/4" MPT

3 13/16" (97)

2 3/4" (70)

5 1/8" (130)

1" MPT

4 1/16" (103)

3 1/8" (79)

5 7/8" (149)

Mounting

Valves are sized to meet the system demand and may
be smaller than the supply lines.

1. Clean the lines upstream from the valve. Remove

any debris > .06" (.15 mm)

2. Install as close as possible to the coil in a vertical

position (actuator over the valve).

CAUTION

: Mount valve with the actuator in the

upright position, or at most a 45° angle, to prevent
condensation collecting in the actuator housing.

3.   Align system flow with arrow on valve.

4. The MPT unions are not provided and must be

ordered separately.

3/4" valves

Order: Three  HMO–5026s

1"  valves

Order: Three HMO–5027s

5. Seal valves with approved valve sealant

6. Allow a minimum clearance of 1-1/2 " (38mm)

between the  top of the actuator and the nearest
obstruction. Allow sufficient side clearance for
servicing the valve.

Required Tools

• digital voltmeter
• small screwdriver
• 2 wrenches