background image

THE-1002 

Installation Guide

Installation Guide

Duct-Mounted Humidity Transmitter w/ Temperature Sensor

THE-1002 

 

Mounting

Mounting 

1

Wiring 

2

More Information  2
Maintenance 

2

Important Notices  2

NOTE:  The sensor should be installed in a straight 

section of duct away from heating, cooling, 

or humidifier elements.

1.  In the duct, drill a 1-1/8" clearance hole (for the 

sensor probe).

2.  Measure 1-5/8" to either side of the center of the 

clearance hole and drill two holes for mounting 

screws.

3.  From the THE-1002, remove the two cover 

screws, cover, and the desired knock-out for the 

conduit.

4.  Insert the THE-1002 probe into the duct.
5.  Insert the two mounting screws and tighten 

them.

6.  Fasten conduit to the THE-1002.
7.  Through the conduit, feed wires to the controller 

and make the appropriate connections. (See the 

Wiring section on the next page.)

8.  After wiring, plug the conduit with plumber’s 

putty, painter’s putty, caulk, or other sealant to 

prevent air infiltration.

9.  Reinstall the cover and cover screws. Be sure 

the screws go through the mounting holes of 

the relay module, securing the back of the relay 

module to the back side of the cover.