KMC Controls THE-1002 Installation Manual Download Page 2

THE-1002 

Installation Guide

© 2013 KMC Controls, Inc.   

859-019-01I

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

The material in this document is for information 

purposes only.

 The contents and the product it de-

scribes are subject to change without notice. KMC 

Controls, Inc. makes no representations or warran-

ties with respect to this document.

 In no event shall 

KMC Controls, Inc. be liable for any damages, direct 

or incidental, arising out of or related to the use of 

this document.

Maintenance

Careful installation will also ensure long-term reli-

ability and performance. Remove dust as necessary 

from the sensing tube.

More Information

For controller configuration 

of the 

humidity input

, see 

the relevant documenta-

tion for the controller and 

software. For controller 

configuration of the 

thermistor input

 as well as 

mounting considerations, 

troubleshooting, and other 

information, see also the 

relevant

 sections in the 

STE-6010/6011/6013/6015 

Application Guide

.

For THE-102 specifications 

and accessory information, 

see the 

THE-1002 Data 

Sheet

.

Wiring

Relay

Module

24 VAC

To

Probe

Cable from Humidity

Sensor in Probe

(Do NOT attempt to

shorten or lengthen

this ribbon cable)

10K Ohm

Thermistor Leads

24 VAC

0-5

VDC

0-10
VDC

4-20

mA

Controller

Temperature Input

Signal Ground

Humidity Input*

*Load between Humidity Input and Signal Ground
  is 250 ohms min. to 650 ohms max. for 4-20 mA
  or 1000 ohms min. for VDC

Phase

Neutral

For power, connect a 24 VAC, Class 2 only, trans-

former (see the diagram).
Connect the desired humidity output (0–5 VDC, 0–10 

VDC, or 4–20 mA) from the THE-1002 to the control-

ler’s humidity input. (Set the controller’s pull-up 

resistor accordingly.)

NOTE:  The thermistor and the humidity output 

have a common output signal ground.

Connect the temperature output (thermistor leads) 

from the THE-1002 to the controller’s temperature 

input. Make wire connections with either butt-splices 

or solder. Using wire nuts is not recommended. (Set 

the controller’s pull-up resistor accordingly.)

NOTE:  The two-wire thermistor leads are polarity 

insensitive.

NOTE:  The relay module mounted inside the 

electrical housing is hard-wired to the 

sensing probe.

 Do not attempt to lengthen 

or shorten the prewired ribbon cable.