STE-6012/6016 Room Temperature Sensors
3
Application Guide, AN0412C Rev. B
Controller Configuration
Overview
For an STE-6012/6016 sensor, the controller will need
two inputs (thermistor and setpoint), one output,
and a common (ground) signal lines.
Since an STE-6012/6016 sensor has 0–5 volt outputs
for both the temperature and the setpoint lines,
turn OFF the corresponding 10,000 ohm pull-up re
-
sistors on the controller board!
Consult the control-
ler’s setup instructions for information on turning off
the pull-up resistors. For the other STE-6000 series
sensors, do
not
turn off the resistors on the controller
board as stated for the STE-6012/6016.
See the relevant software section for controller
configuration instructions.
12. Click
Defaults
(values will fill in).
13. Click
End Edit
.
14. Click
Yes
for “Send Update Notification Now?”
15. Click
OK
.
Setpoint Input
NOTE: On the controller board, turn OFF the
10,000 ohm pull-up resistor.
1. In the BACstage software main menu, select
Objects
>
Inputs
(if the screen was closed
previously).
2. Click
Edit
.
3. Type in a name in the appropriate
Description
field and/or
Name
field.
4. Select
Object Type: Analog
if it is not the default.
5. Select
Device Type: Custom
(at the bottom of the
list).
6. In the upper field, type 40, and in the lower field,
type 90 (or 4 and 32 for Celsius).
7. Click
Calculate Offset and Multiplier
.
8. Click
OK
.
9. Click
End Edit
.
10. Click
Yes
for “Send Update Notification Now?”
11. Click
OK
.
Supply Voltage
NOTE: The STE-6012/6016 is powered by the
controller on terminal D or the green wire.
With 7.5 VDC applied, the sensor is in
setback/unoccupied mode; with 12 VDC
applied, the sensor is in normal/occupied
mode.
Pressing the
Down
button momentarily
sends 0 VDC to the controller for a
SENSORON
signal on terminal C or
orange wire; pressing the
Up
button sends
greater than 5 VDC for a
SENSOROFF
signal.
Pressing a button raises or lowers the
setpoint voltage. When in unoccupied
mode, pressing either button selects
override mode (and “OVERRIDE” is
shown on the LCD display). “OVERRIDE”
will continue to be displayed until the
voltage is restored to 12 VDC.
To remove
“OVERRIDE” from the display at the end
of a timed override period, momentarily
change the voltage to 12 VDC and then
BACstage Software
Room Temperature (Thermistor) Input
NOTE: On the controller board, turn OFF the
10,000 ohm pull-up resistor.
1. In the BACstage software main menu, select
Objects
>
Inputs
.
2. Click
Edit
.
3. Type in a name in the appropriate
Description
field (up to 32 characters) and/or
Name
field (up
to 16 characters).
NOTE: No two labels or descriptions in a controller
can be identical.
4. Select
Object Type: Analog
if it is not the default.
5. Select
Device Type: KMC10K Type II
.
6. Select
Units: °F
or
°C
.
7. Optionally, change the
Filter Weight
(under
More
)
to the desired number of thermistor readings
averaged before displaying the result.
If the
override is being used,
Filter Weight
may need
to be reduced down toward 1 to ensure reliable
recognition of the button press, depending on
the controller.
NOTE: The Up and Down buttons need to be
pressed and held for at least a half a
second to be reliably recognized for
override mode.
8. Click
End Edit
.
9. Click
Yes
for “Send Update Notification Now?”
10. In the BACstage software main menu, select
Device
>
Device Tables
>
KMC10K Type II Table
.
11. Click
Edit
.