REE-2002 

Installation Guide

Installation Guide

Mounting 

1

Connections and Wiring  1
Specifications  2
Troubleshooting  2
Maintenance 

2

More Information  2
Important Notices  2

Mounting

The 

module may be mounted directly to a control 

box surface or in a 2 x 4" electrical handy box. Add a 

blank cover to conceal the module if desired.

Connections and Wiring

1.  Connect a controller input to 

one

 of the three 

THE-1102/REE-2002 (0–5 VDC, 0–10 VDC, 4–20 

mA) outputs as shown in the sample illustration 

below.

2.  Connect the B, F, C, and D terminals to the 

corresponding terminals on the THE-1102.

3.  Supply the REE-2002 with 24 VAC (+20%/–15%) 

from a Class 2 transformer (only).

Power Supply and E-E/I Converter Module

REE-2002

  

REE-2002

24 VAC

GND

24 VAC

0-5 VDC

0-10

VDC

4-20

mA

F

C

D

B

THE-1102

Humidity Output

(0-5 VDC)

(Without the REE-2002, only the THE-1102’s 0-5 VDC humidity

output and thermistor signal are available to a controller)

Temp. Output

(10K Thermistor)

Signal Ground

– Power Ground

+ 10-15 VDC Power

F

C

D

B

A

Controller

Temp. Input

Signal Ground

Humidity Input*

+

Phase 

Neutral

*Load between Humidity Input and Signal Ground
  is 250 ohms min. to 650 ohms max. for 4-20 mA
  or 1000 ohms min. for VDC

NOTE:  Use wire size 14 to 22 AWG, stranded.
NOTE:  See also the 

THE-1102 Installation Guide

 

for additional information about this 

application. (The THE-1101 has been 

discontinued.)