![KMC Controls MEP-4 Series Application Manual Download Page 11](http://html.mh-extra.com/html/kmc-controls/mep-4-series/mep-4-series_application-manual_1979480011.webp)
MEP-4xxx Direct-Coupled Actuators (40 to 90 in-lb.)
11
Applications Guide, AN0513A Rev. J
MEP-4xx1/4x13 Tri-State Wiring Configuration
CW
COM
CCW
Switch Position:
1 = Rotation is
Direct
0 = Rotation is
Reversed
–
~
Feedback Potentiometer
(MEP-4x13 Only)
Power
Supply
Power/Signal
Terminal Block
Selector
Switches
Power/Signal
Cable
Aux. Switch
Cable
(Under Conduit Fitting)
MEP-42xx/45xx/49xx Options
Tri-State/2-Position Rotation Direction
Tri-state/two-position MEP-4xx1/4xx3 models (ex
-
cept MEP-4003) have switches
for selecting rotation
direction. Be sure switches are set correctly for the
application.
• Non-fail-safe MEP-4xx1/
4x13 models (beginning
in Jan. 2014) have a slide switch to the right
of the terminal block. See the
Two-Position Wiring (MEP-4001/3/4/5)
MEP-4xx4/4xx5 two-position actuators have “tradi
-
tional” two wires for 24 VAC/VDC or 100–250 VAC
signal/power.
• Fail-safe MEP-4x51 and fast-acting MEP-4x01
models have selector switches to the left of the
terminal block. See the
for more information.
(FS) MEP-4x51 Two-Position Control, CW Leg (Four-Wire)
–
Power Supply
24 VAC/VDC
Contact Position:
Closed = CW Rotation
CW
CCW
T COM
~24 V
~/+
Open = CCW Rotation
Switch Position
1 2
(Fail-Safe) MEP-4xx4 Two-Position 24 VAC/VDC (Two-Wire)
–
Power Supply
24 VAC/VDC
T COM (Blac
k)
~24
V (Red)
~/+
Starting in January 2014,
tri-state
MEP-4xx1/4xx3
models (except MEP-4003)
also offer two-position
functionality
as an option. That option is dependent
on wiring configuration and selector switch position.
See
Tri-State/2-Position Rotation Direction on page
. The (tri-state) two-position
option requires
“three-wire” (non-fail-safe) or “four-wire” (fail-safe)
wiring configuration.
(NFS) MEP-4x01 Two-Position Control, CW Leg (Three-Wire)
– Power Supply
24 VAC/VDC
Contact Position:
Closed = CW Rotation
CW
CCW
T COM
~/+
Open = CCW Rotation
Switch Position
1 2
MEP-4200/4500/4900 Series Installation
See the
MEP-4201/4501/4901 Installation Guide
MEP-4000/4800 Series Installation Guide
information.