Installation Guide

© 2017 KMC Controls, Inc.   

016-019-01B

Important Notices

The material in this document is for information pur-

poses only. 

The contents and the product it describes 

are subject to change without notice.

 KMC Controls, 

Inc. makes no representations or warranties with respect 

to this document. In no event shall KMC Controls, Inc. 

be liable for any damages, direct or incidental, arising 

out of or related to the use of this document.

Maintenance

No routine maintenance is required. However, 

care should be taken during any installation or 

maintenance due to the power of the actuator. Each 

component is designed for dependable, long-term 

reliability, and performance. Careful installation will 

also ensure long-term reliability and performance.

Adjustments and Calibration

 DANGER

The MCP-1060 contains a large powerful spring. 
Exercise extreme caution if disassembly is required. 
The actuator shaft MUST be restrained to prevent 
the spring from expanding.

To change the positioner start-point:
1.  Apply the desired signal pressure.
2.  Rotate the start-point adjuster until the actuator 

starts to stroke.

More Information

For specifications and other information about the 

actuators, see the 

MCP-1160 Series Data Sheet 

on 

the

 

KMC web site

. For information about the posi-

tioner, see 

CMC-1001 Data Sheet

.

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Connections

NOTE

:  Use 1/4" (6 mm) O.D. FR polyethylene 

tubing and only clean, dry control air.

NOTE

:  MCP-1160 models ordered with CMC-1001 

positioners are factory-piped between the 

positioner and the actuator.

1.  Connect the 

input control signal

 to the actuator 

port (if no positioner is used) or to the positioner 

(CMC-1001 input) Port 

2

 (see the diagram).

2.  Connect the 

main air

 (20 psi) to the positioner 

(CMC-1001 center) port.

3.  If a positioner is not factory-piped to the actuator, 

connect the actuator input port to positioner 

(CMC-1001 output) Port 

1

.

NOTE

:  If the application requires operation near 

the maximum temperature and maximum 

pressure, add a tubing restraint to the 

actuator connection.

The MCP-1160 contains an 8-13 psi spring. A CMC-

1001 positioner allows the unit to operate over any 5 

psi span with the start-point adjustable from 3-10 psi. 

Replace the 5 psi spring with a 7 or 10 psi spring to 

widen the span.