![KMC Controls KMD-5551E Application Manual Download Page 21](http://html.mh-extra.com/html/kmc-controls/kmd-5551e/kmd-5551e_application-manual_1979491021.webp)
Sec ti o n 3:
Co n f i gu r i n g th e K M D- 5551E
tr an s l ato r
This section provides important guidelines for configuring a translator before it is placed
on a network. Review this information carefully for proper installation.
The translator must be configured as a network device. To prevent disrupting an existing
network, configure the network address before connecting the translator to the network. The
BACnet device instance and other properties can be configured at the same time or after the
translator has an IP address assigned and it is installed in its permanent location on a
network.
Topics in this section
Initial setup
Configure the KMD-5551E translator with an HTML5 compatible web browser using the web
pages served from within the translator. The translator has the following default network
address values.
l
IP address—192.168.1.252
l
Subnet mask—255.255.255.0
l
Gateway—192.168.1.1
You will need the following information before you can configure a translator.
From the BACnet system engineer:
l
BACnet device instance for the translator.
l
Network numbers for each of the enabled networks.
l
If applicable, the address and port for a PAD router or BBMD to which the translator will
connect.
From the IT system administer:
l
The IP address for the translator.
l
The IP subnet mask for the Ethernet LAN to which the translator will connect.
l
The IP address of the network gateway.
KMD-5551E Translator
Revision B
21