HPO-6700 Series Output Override Boards Installation Guide
4 902-019-02K
NOTE:
Each of the override slots ships from
KMC with a jumper installed on the
two pins closest to the output terminal
blocks. Only remove a jumper if an
override board will be installed.
4. Orient the override board with the HOA
selection slide
switch toward the outputs
of
the controller.
5. Slide the override
board into the slot
in which
the jumper was removed.
6. Move the
A-O-H
selection switch
on the
override board to the appropriate position.
NOTE: H
= Hand/On.
O
= Off.
A
= Automatic.
7. Repeat steps 3 through 6 for all desired
boards.
8. Remove the necessary label slots for each
board location in the
HPO-6802 output board
cover
(purchased separately).
9. Snap the HPO-6802 cover over the boards.
10. Connect output devices to the controller
outputs. (See
Wiring on page 4
.)
11. Reinstall the power jumper or terminal block
that was removed in Step 1.
6. Set the selection switch on the override board
to the appropriate position.
NOTE: A
= Automatic (upper position).
O
= Off (middle position).
H
= Hand/On (lower position).
7. Repeat steps 3 through 6 for all desired
boards.
8. Reinstall the cover over the boards.
9. Connect output devices to the controller
outputs. (See
Wiring on page 4
.)
10. Reinstall the power jumper that was removed
in Step 1.
1
2
3
4
8
OLDER "METAL" CASE CONTROLLERS
These instructions apply to controllers with
metal
(e.g., BAC-5831, BAC-A1616BC)
and older
“side-mounting” plastic cases
(e.g.,
older KMD-
5801/5802). After installation of the boards, the
existing slot cover needs to be replaced by a
raised HPO-6802 output board cover.
To install the HPO-6700 series override boards:
1. Disconnect the power by removing the
power
jumper or terminal block
.
2. Remove the relevant slot
cover
(s) by lifting the
right-hand side of the cover (within the plastic
frame) toward you.
3. Remove the
jumper
from the slot in which the
override board will be installed.