Barber Colman TP-81xx Thermostats Replacement Applications
54
CTE-5202 Applications Guide, AN0912A Rev. D
Barber Colman TP-81xx Thermostats
Replacement Applications
This section gives sample applications for using the
CTE-5202 in the place of a Barber Colman (TAC,
Invensys, Schneider Electric) TP-81xx thermostat.
Some of the applications include use with
MP-52xx
“beer can” actuators.
TP-8101, TP-8102,
and TP-8103 Leads
and Terminals
Function
CTE-5202 Terminals
Red Wire Lead
+20 VDC
~
(Phase)
Yellow Wire Lead
Proportional
Output
AO1
Blue Wire Lead
Common
T
(Common)
Terminal 1
Common
T
(Common)
Terminal 2
Auxiliary Input
AI1
NOTE: Use Sequence 1. See sample applications on
.
TP-8124 and
TP-8125 Terminals
Function
CTE-5202
Terminals
OP2
2–15 VDC Cooling (DA)
AO1
+20
+20 VDC (Input)
~
(Phase)
OP1
15–2 VDC Heating (RA)
AO2
Com
Common
T
(Common)
NOTE: Use Sequence 3. See sample applications on
.