KMC Controls CTE-5201 Installation And Operation Manual Download Page 3

CTE-5201 

     3 

Installation and Operation Guide

Configuration

Operation

Changing Defaults

The factory default settings are:
•  Setpoint (Default):  70 F
•  MAX: 

 

 100%

•  MIN: 

 

 20%

•  F/C Mode:  

 Degrees F

•  UNOCC Mode:   Off
•  PROP: 

 

 4 F

•  INT: 

 

 30 Minutes

To change configuration values

:

1.  Flip open the cover (hinged on the left side).
2.  Push the desired button to display the value to be 

changed.

3.  Use the Up/Down buttons to change the value 

(except for toggling between °F and °C, which 

uses the F/C button only)

4.  Press and hold the corresponding button for 

approximately 10 seconds until after the display 

starts flashing (and the new value is stored in 

memory).

MAX

This is the 

maximum

 (high limit) value (

HL

%

) that 

the output can attain. It is adjustable up to 100% (10 

volts) and down to the MIN setting.

MIN

This is the 

minimum

 (low limit) value (

LL

%

) that 

the output can attain. It is adjustable down to 0% (0 

volts) and up to the value of the MAX setting.

F/C 

To toggle between 

degrees F and C MODES

 (se-

lected scale persists), press and hold the F/C button 

(only) down for about 10 seconds (do not use the 

Up/Down buttons) until the display begins to flash. 

Room temperature, setpoint, proportional band, 

deadband, and offset will thereafter be displayed in 

the desired units. See also 

Toggle Between °F and °C 

on page 3

.

UNOCC

Momentarily pressing this button will put the unit 

into the 

Unoccupied

 mode (

Unoc

).

 

It will stay in 

this mode until either the Setpoint or Up/Down 

buttons are pushed. There are two unoccupied mode 

options, Off (the default) or Deadband:
•  In 

Off Mode 

(

OFF

), the output voltage is forced 

to 0 VDC (0%). If the room temperature falls 

Turn On Backlight

Pressing any button turns on the backlight, which 

will remain on until about nine seconds after the last 

button press.

Change Setpoint

To change the setpoint, push the Setpoint button to 

display the current value. Use the Up/Down buttons 

to change the value. After the display reverts back 

(after about nine seconds) to displaying the room 

temperature, the thermostat will control at the new 

setpoint.

NOTE:  After a power loss, the setpoint will revert 

to the default value (70° F or 21.1° C is the 

factory default). This default value is also 

used in the deadband unoccupied mode. To 

change the default value, 

see 

Configuration 

on page 3

.

Start Unoccupied Mode

Flip open the cover (hinged on the left side) and 

momentarily push the UNOCC button. The thermo-

stat will stay in Unoccupied mode until the Setpoint 

button or one of the Up/Down buttons are pushed.

NOTE:  There are two unoccupied mode options, 

Off (the default) or Deadband. S

ee 

Configuration on page 3

 for details.

Toggle Between °F and °C

To 

temporarily

 view the other temperature scale, flip 

open the cover (hinged on the left side), and momen-

tarily press the F/C button. The alternative scale will 

appear as long as the backlight is on.
To make the desired F or C scale mode 

permanent

 

(the scale persists instead of being momentary), press 

and hold the F/C button down for approximately 10 

seconds until the display begins to flash. To return to 

the previous scale mode, repeat the process.

Summary of Contents for CTE-5201

Page 1: ...Additional Information on page 4 from touching the circuit board in the thermostat use only the mounting screws supplied by KMC Controls Using other screws may damage the thermostat Do not turn screws in farther than necessary to remove the cover 2 Route the cable through the backplate 3 With the hex screws toward the floor fasten the backplate to the outlet box with the supplied screws The backpl...

Page 2: ...le 12 foot length between actuators Wires Orange Orange Stripe T Wires Green Green Stripe XEE 6xxx xxx Transformer 24 VAC 20 15 4 VA Per Actuator HSO 2250 Thermostat Cable 50 foot typical Cable P N Cable Length HSO 2203 3 feet HSO 2206 6 feet HSO 2212 12 feet HSO 2220 20 feet HSO 2250 50 feet Modular to Leads HSO 5012 Cable If using the HSO 5012 cable plug the modular con nector into the thermosta...

Page 3: ...tons are pushed There are two unoccupied mode options Off the default or Deadband In Off Mode OFF the output voltage is forced to 0 VDC 0 If the room temperature falls Turn On Backlight Pressing any button turns on the backlight which will remain on until about nine seconds after the last button press Change Setpoint To change the setpoint push the Setpoint button to display the current value Use ...

Page 4: ...perature closer to the default occupied setpoint temperature than the Off Mode PROP The proportional band Pb is the temperature band around the setpoint over which the output will vary from MIN to MAX due to the proportional action alone The proportional band is adjustable from 2 to 6 F 1 1 to 3 3 C INT As long as there is an error between room tempera ture and setpoint the integral action In will...

Reviews: