CTE-5201 

     1 

Installation and Operation Guide

Mounting the Thermostat

1.  If the thermostat is 

locked on the backplate, 

turn the two hex screws 

(in the 

two outermost 

holes

) in the backplate 

CLOCKWISE

 until they (just) clear the cover. 

Swing the thermostat up and away from the 

backplate to remove it.

 CAUTION

To prevent damage to the board, do not insert 
a screwdriver into any holes other than the two 
outermost holes. To prevent mounting screw heads 

Installation and Operation Guide

Electronic Room Thermostat (Modular)

CTE-5201

 

Mounting

Rough-in Preparation

For optimum temperature sensor performance, the 

thermostat must be mounted on an interior wall 

and away from heat sources, sunlight, windows, 

air vents, and air circulation obstructions (e.g., 

curtains, furniture).

Complete rough-in wiring prior to installation:
•  Route the cable from the thermostat location to 

the actuator to which it will connect. See 

Wiring 

on page 2

.

•  If needed, install the HMO-1161 mounting 

backplate. See 

Additional Information on page 4

.

from touching the circuit board in the thermostat, use 
only the mounting screws supplied by KMC Controls. 
Using other screws may damage the thermostat. Do 
not turn screws in farther than necessary to remove 
the cover.

2.  Route the cable through the backplate.
3.  With the hex screws toward the 

floor, fasten the backplate to the 

outlet box with the supplied screws. 

(The backplate mounts directly on 

vertical

 2 x 4 inch boxes, but re-

quires an HMO-1161 wall mounting 

plate for horizontal or 4 x 4 boxes.) 

4.  Insert the modular end of the cable 

into the jack of the thermostat.

5.  Place the top of the thermostat over the top of 

the mounting base and swing it down over the 

hex screw brackets. Be careful not to pinch the 

wiring.

6.  Back the hex screws out of the backplate brackets 

(

counterclockwise) 

until they engage the ther-

mostat and hold it in place.

A

B

C

E F

RJ-12 
Modular 
Connector

D

Pin 6

Pin 1

Mounting 

1

Rough-in Preparation 

1

Mounting the Thermostat 1

Wiring 

2

Modular to Modular (HSO-22xx Cable) 

2

Modular to Leads (HSO-5012 Cable)  2

Operation 

3

Turn On Backlight  3
Change Setpoint 

3

Start Unoccupied Mode  3
Toggle Between °F and °C 

3

Configuration  3

Changing Defaults  3
MAX 

3

MIN 

3

F/C  

3

UNOCC 

3

PROP 

4

INT 

4

Calibration (Temperature Offset) 

4

Maintenance 

4

Additional Information  4

Pin 1 and 6

Pin 2 and 5

Pin 3

Pin 4

N/C

Common

Supply 

(14–19 VDC)

Output 

(2–10 VDC)*

*0 VDC during Unoccupied Off mode when temperature stays 

above 50° F

A

3.25 

in.

83 

mm

B

5.16 

in.

116 

mm

C

0.88 

in.

22 

mm

D

0.38 

in.

10 

mm

E

2.58 

in.

66 

mm

F

3.25 

in.

83 

mm

Summary of Contents for CTE-5201

Page 1: ...Additional Information on page 4 from touching the circuit board in the thermostat use only the mounting screws supplied by KMC Controls Using other screws may damage the thermostat Do not turn screws in farther than necessary to remove the cover 2 Route the cable through the backplate 3 With the hex screws toward the floor fasten the backplate to the outlet box with the supplied screws The backpl...

Page 2: ...le 12 foot length between actuators Wires Orange Orange Stripe T Wires Green Green Stripe XEE 6xxx xxx Transformer 24 VAC 20 15 4 VA Per Actuator HSO 2250 Thermostat Cable 50 foot typical Cable P N Cable Length HSO 2203 3 feet HSO 2206 6 feet HSO 2212 12 feet HSO 2220 20 feet HSO 2250 50 feet Modular to Leads HSO 5012 Cable If using the HSO 5012 cable plug the modular con nector into the thermosta...

Page 3: ...tons are pushed There are two unoccupied mode options Off the default or Deadband In Off Mode OFF the output voltage is forced to 0 VDC 0 If the room temperature falls Turn On Backlight Pressing any button turns on the backlight which will remain on until about nine seconds after the last button press Change Setpoint To change the setpoint push the Setpoint button to display the current value Use ...

Page 4: ...perature closer to the default occupied setpoint temperature than the Off Mode PROP The proportional band Pb is the temperature band around the setpoint over which the output will vary from MIN to MAX due to the proportional action alone The proportional band is adjustable from 2 to 6 F 1 1 to 3 3 C INT As long as there is an error between room tempera ture and setpoint the integral action In will...

Reviews: