Installation Guide

Differential Pressure Switches

CSE-1102/1103   

 

Mounting

Select a mounting location that is free from vibration. 

Mount in any vertical plane in order to obtain the 

lowest specified operating setpoint. Avoid mounting 

with the sample line connections in the “up” posi-

tion. Surface mount via the two 3/16" diameter holes 

in the integral mounting bracket. The mounting 

holes are 3-7/8" apart.
1.  Align the unit vertically with the barbed ports 

at the bottom (alternately pointing to the left or 

right).

2.  Using the two 3/16" mounting holes, attach to the 

ducting.

3.  Using the knockout, attach a 1/2" conduit.
4.  Connect wires to the screw terminals. See the 

Wiring section.

Connecting Sensing Ports

NOTE:  A sampling probe should be located 

a minimum of 1.5 duct diameters 

downstream from the air source. Install the 

sampling probe as close to the center of the 

airstream as possible.

NOTE:  For sample lines of up to 10 feet, 1/4" OD 

tubing is acceptable. For lines up to 20 feet, 

use 1/4" ID tubing. For lines up to 60 feet, 

use 1/2" ID tubing.

To attach a sampling line:
•  To a CSE-110

2

 with barbed connections, use 1/4 

to 3/8" (6 to 9 mm) tubing for air sampling lines 

and connect the tubing to the appropriate port(s).

•  To a CSE-110

3

 with compression connections, 

connect 1/4" OD copper to the compression 

fitting(s).

Connect the sampling lines according to the applica-

tion:

•  Positive Pressure Only:

 Connect the sample line 

to inlet H. (Inlet L remains open to the atmo-

sphere.)

•  Negative Pressure Only:

 Connect the sample line 

to inlet L. (Inlet H remains open to the atmo-

sphere.)

•  Two Negative Samples:

 Connect the higher 

negative sample to inlet L. Connect the lower 

negative sample to inlet H.

•  Two Positive Samples:

 Connect the higher posi-

tive sample to inlet H. Connect the lower positive 

sample to inlet L.

•  One Positive and One Negative Sample:

 Con-

nect the positive sample to inlet H. Connect the 

negative sample to inlet L.