BAC-19xxxx FlexStat Installation Guide 

2 926-019-02C

WIRING CONSIDERATIONS

See the 

BAC-19xxxx FlexStat Sequence of Oper-

ation and Wiring Guide 

for sample wiring for dif-

ferent applications. 

See the 

BAC-19xxxx FlexStat 

Application Guide

 for additional important wiring 

considerations.

   CAUTION  

The BAC-19xxxx models are 

NOT compatible with the 

backplates of older BAC-

10xxx/12xxxx/13xxxx/14xxxx 

FlexStats! If replacing an older 

FlexStat, replace the backplate as 

well.

•  Because of the many connections (power, 

network, inputs, outputs, and their respective 

grounds or switched commons), 

be sure wiring 

is well planned before installation of conduit!

• 

Make sure that conduit for all wiring has 

adequate diameter for all necessary wiring.

 

Using 1-inch conduit and junction boxes is 

recommended! Use external junction boxes 

above the ceiling or in another convenient 

location as needed to make connections that 

run to the FlexStat’s junction box.

•  To prevent excessive voltage drop,

 use a 

conductor size that is adequate for the wiring 

length! Allow plenty of “cushion” to allow for 

transient peaks during startup.

•  Using 

multiple conductor wires

 for all inputs 

(e.g., 8 conductor) and outputs (e.g., 12 

conductor) is recommended. Grounds for all 

the inputs can be combined on one wire.

MOUNTING

A

C

B

Terminal Blocks 

on Backplate

Optional 

Ethernet Jack 

on Back of 

Cover

Cover Locking Screw

Embossed “UP” Indicator

DIMENSIONS

A

3.874 inches

99.4 mm

B

5.124 inches

130.1 mm

C

1.301 inches

33.0 mm

Illustration 1—Dimensions and Mounting Information

NOTE: 

For optimum temperature sensor 

performance, the FlexStat must be 

mounted on an interior wall and 

away from heat sources, sunlight, 

windows, air vents, and air circulation 

obstructions (e.g., curtains, furniture). 

Additionally, for a model with an 

occupancy sensor option, install it 

where it will have unobstructed view 

of the most typical traffic area. See 

the 

Room Sensor and Thermostat 

Mounting Location and Maintenance 

Application Guide

.

NOTE: 

If replacing an existing thermostat, 

label wires as needed for reference 

when removing the existing 

thermostat.

1.  Complete rough-in wiring at each location prior 

to FlexStat installation. Cable insulation must 

meet local building codes.

   CAUTION 

Use only the mounting screw supplied 

by KMC Controls. Using other screws 

may damage the FlexStat. Do not turn 

the screw in farther than necessary to 

remove the cover.

2.  If the cover is locked on the backplate, turn the 

hex screw

 in the bottom of the FlexStat 

clock-

wise

 until the screw (just) clears the cover. 

(See Illustration 1.)

Summary of Contents for BAC-19 FlexStat Series

Page 1: ...g an older FlexStat replace the backplate as well NOTICE OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES KMCConquestTM Automation Hardware QUICK START Complete the following steps to select and install a KMC Conquest BAC 19xxxx FlexStat 1 Select the appropriate model for the intended application and options see the BAC 190000 Series FlexStats Data Sheet at kmccontrols com 2 Mount ...

Page 2: ...outputs e g 12 conductor is recommended Grounds for all the inputs can be combined on one wire MOUNTING A C B Terminal Blocks on Backplate Optional Ethernet Jack on Back of Cover Cover Locking Screw Embossed UP Indicator DIMENSIONS A 3 874 inches 99 4 mm B 5 124 inches 130 1 mm C 1 301 inches 33 0 mm Illustration 1 Dimensions and Mounting Information NOTE For optimum temperature sensor performance...

Page 3: ...and Wiring Guide and the BAC 19xxxx FlexStat Application Guide Illustration 5 BAC 19xx63 Terminals and Connections B A IN7 IN6 GND IN5 IN4 IN3 GND IN2 Common C Phase R Analog 9 GND 7 9 Analog 8 Analog 7 Relay 6 SC 4 6 Relay 5 Relay 4 Relay 3 SC 1 3 Relay 2 Relay 1 Outputs Wiring Cutout in Backplate MS TP Network Optional Inputs 24 VAC Wiring is dependent on application Ethernet Network Connector O...

Page 4: ... TP network see Planning BACnet Networks Application Note AN0404A A Connect the A terminals in parallel with all other A terminals on the network B Connect the B terminals in parallel with all other B terminals on the network C Connect the shields of the cable together at each device using a wire nut or the S terminal in other KMC BACnet controllers CAUTION When reinstalling the cover on the backp...

Page 5: ...PMENT CONNECTIONS Input Connections 1 Wire any additional sensors to the appropriate input terminals See the BAC 19xxxx FlexStat Sequence of Operation and Wiring Guide These applications are the selectable pack aged programs in the BAC 19xxxx models NOTE Use KMC software to properly configure the devices For passive input devices e g switch contacts and 10K ohm thermistors set the termination to t...

Page 6: ...other communication issues in networked MS TP model FlexStats correct phasing on MS TP network and power connections on ALL the networked controllers is critically important NOTE Follow all local regulations and wiring codes 2 Connect a 24 VAC Class 2 transformer or 24 VDC power supply to the power terminals see Illustration 12 A Connect the neutral side of the transform er to the common C termina...

Page 7: ... Cool Auto Off Mode Active Heating Setpoint Units F or C Illustration 13 Screen Menus Access Default NOTE Options in menus are dependent on the FlexStat model and selected application Advanced configuration of a FlexStat can be done through software See the BAC 190000 Series FlexStats Data Sheet for the most relevant KMC Controls tool for additional configuring program ming with Control Basic and ...

Page 8: ...logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com 2022 KMC Controls Inc Specifications and design subject to change without notice 926 019 01C ADDITIONAL RESOURCES The latest support files are always available on the KMC Controls web site www kmccontrols com To see all available files you will need to log in See the ...

Reviews: