Digital I/Os 

„

 

Inputs may be wired as either pnp (source) or npn (sink) inputs. 

npn (sink) inputs 

pnp (source) inputs 

0V

+V

Circuit Protection Device

 

0V

+V

 

npn (sink)  

high-speed counter/frequency measurer 

pnp (source )  

high-speed counter/frequency measurer 

0V

+V

Circuit Protection Device

High-speed

Counter

Reset

High-speed

Counter

0V

+V

High-speed

Counter

Reset

High-speed

Counter

 

 

www.klinkmann.com

5 / 2011

Summary of Contents for Unitronics IO-DI8-RO8

Page 1: ...pts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of this equipment...

Page 2: ...not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounti...

Page 3: ...nics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 www klinkmann com 5 2011 ...

Page 4: ... before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough to keep the ...

Page 5: ...sink inputs npn sink inputs pnp source inputs 0V V Circuit Protection Device 0V V npn sink high speed counter frequency measurer pnp source high speed counter frequency measurer 0V V Circuit Protection Device High speed Counter Reset High speed Counter 0V V High speed Counter Reset High speed Counter www klinkmann com 5 2011 ...

Page 6: ...ltage power supply specifications connect the device to a regulated power supply Notes 1 The adapter and output s power supply must be connected to the same 0V signal Outputs Circuit Protection Device L1 L2 L3 115 230VAC V 12 24VDC Output s power supply 0V V N 0V Load See Note 1 Increasing Contact Life Span Both modules have 8 relay outputs To increase the life span of these contacts and protect t...

Page 7: ...C 4 3mA for Logic 1 Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80μs Outputs Number of outputs 8 relay Output type SPST NO Form A All relays share a common signal Isolation By relay...

Page 8: ...cates the I O s location in the system This number relates to both the position of the expansion module in the system and to the position of the I O on that module Expansion modules are numbered from 0 7 as shown in the figure below 0 1 2 3 4 5 6 7 Expansion module identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the OPLC X is the...

Reviews: