MJ20-ET1
Wiring
Do not touch live wires.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply
Ethernet Wiring—General
Use standard Ethernet shielded cable.
Earthing the MJ20-ET1
To maximize system performance, avoid electromagnetic interference as follows:
Connect the functional earth terminal ( ) directly to the earth ground of the system.
Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm
2
(14AWG) min, wires possible.
MJ20-ET1 Technical Specifications
Port type
10/100 Base-T (RJ45)
Cable type
Shielded CAT5e cable,
up to 100m (328 ft)
Auto crossover
Yes
Auto negotiation
Yes
Galvanic isolation
Yes
Weight
15g (0.53 oz)
Environmental
Ingress protection
IP
20
, NEMA
1
Operational
temperature
0°C to 50°C (32°F to 122°F)
Storage
temperature
-20°C to 60°C (-4°F to 140°F)
Relative Humidity
(RH)
5% to 95% (non-condensing)