Klimawent WPA-P-N Use And Maintenance Manual Download Page 6

 

                                                      

portable radial fans 

  

WPA

-

P

-

N

                              04.06.2019 

 

 

     

 

4.1  Information pertaining to energetic efficiency for fans  

– according to Regulation of Committee (EU) No. 327/2011

 

Table No.3 

Product information 

requirements 

WPA- 

3-1 

WPA- 

5-1 

WPA- 

5-3 

WPA- 

6-1 

WPA- 

6-3 

WPA- 

7-1 

WPA- 

7-3 

WPA- 

8-3 

WPA- 

9-3 

WPA- 

10-3 

1  Overall efficiency (%) 

51 

67,6 

70 

54,1 

61,1 

65,1 

65,6 

62,2 

67 

66,1 

2  Measurement category 

(A-D) 

3  Efficiency category 

static 

4  Efficiency grade at 

optimum energy efficiency 

point  (%) 

43,9 

47,9 

48,1 

50,6 

48,7 

50,5 

51,4 

52,2 

53,3 

55,9 

5  Did the efficiency 

calculation use VSD? 

no 

6  Year of manufacture 

see nominal data plate 

7a Manufacturer’s name 

see nominal data plate 

7b Commercial registration 

number 

see nominal data plate 

7c  Place of manufacturing 

see nominal data plate 

8  Model number 

see nominal data plate 

9a Rated motor power input 

(kW) 

0,25 

0,37 

0,37 

0,75 

0,75 

1,1 

1,1 

1,5 

2,2 

3,0 

9b Flow rate at the optimum 

Energy efficiency (m

3

/h) 

700 

1430 

1180 

1580 

1250 

2000 

1870 

2030 

2230 

3750 

9c  Pressure at the optimum 

Energy efficiency (Pa) 

620 

970 

1000 

1270 

1360 

1400 

1400 

1595 

2000 

1700 

10 Rotations per minute at 

the optimum efficiency 

point (r.p.m.) 

2760 

2770 

2790 

2800 

2870 

2770 

2870 

2880 

2880 

2880 

11 Specific ratio 

1,007 

12 Fan disassembly, 

recycling and disposal at 

the end of operational life  

see the sections concerning the maintenance and recycling  

13 To minimalize the 

environmental impact and 

ensure the optimal live 

expectancy of the fan 

follow maintenance instructions of the fan 

14 Description of additional 

items applied for 
determining the energe- 

tic efficiency of the fan 

not supplied with the fan 

 

 

5.

 

Structure and Function 

 

The fan consists of a steel spiral housing  and a motor  and a radial impeller  which is directly 
mounted on the motor shaft (direct drive).

  

The structure rests on a base frame structure. 

The

 

inlet and outlet are adapted for connection of the flexible hoses,

 which

 are clamped with hose 

clamps. For safety reasons,

  

the

 inlet and outlet are equipped with a protective grill.  The impel- 

ler with profiled radial blades provides low acoustic pressure of the fan.   

As standard

,  the fan is equipped with a motor protective switch

.

  

Each fan is energized through

  

a five metre long power supply cable with a plug. 
 

6.

 

Assembly and Start-up 

The portable WPA-P-N fans can work in closed rooms

 (indoor application) 

and outside the buil- 

dings.  In case of outdoor application (especially for a longer time of operation) it is important  
to protect the device against atmospheric factors. 

 

Summary of Contents for WPA-P-N

Page 1: ...1 04 06 2019 portable radial fans WPA P N Use and Maintenance Manual Portable radial fans WPA P N...

Page 2: ...ervations of Producer 4 4 Technical Data 4 5 Structure and Function 6 6 Assembly and Start up 6 7 Operational Use 8 8 Troubleshooting Guide 8 9 Maintenance and Control 9 10 Occupational Health and Saf...

Page 3: ...to the making available on the market of electrical equipment designed for use within certain voltage limits Journal of Laws EC L96 of 29 03 2014 The appliance meets the requirements included in 2009...

Page 4: ...ces in form of gas vapour mist and dust that in connection with the air create the explosive atmosphere F Do not use the fan for conveying the air containing viscous impurities that could accumulate o...

Page 5: ...1 N 475 440 1 160 160 520 440 425 235 500 WPA 5 P 3 N WPA 6 P 1 N 475 440 1 160 160 500 450 450 245 525 WPA 6 P 3 N WPA 7 P 1 N 615 515 355 200 160 615 515 480 285 585 WPA 7 P 3 N WPA 8 P 3 N 615 515...

Page 6: ...2790 2800 2870 2770 2870 2880 2880 2880 11 Specific ratio 1 007 12 Fan disassembly recycling and disposal at the end of operational life see the sections concerning the maintenance and recycling 13 T...

Page 7: ...the correctness of the electrical connections the impeller rotation sense ought to be accor ding to the arrow on the housing if this is the opposite change the phase connection sequence Approaching wi...

Page 8: ...an can be placed outside the building the drying air has to be forced through an air supply hose into the humid room Here it is important to protect the fan from atmospheric factors by a hood cover In...

Page 9: ...and Safety Start up and the operational use is only admissible exclusively after getting acquainted with the contents of the present Use and Maintenance Manual Connect the fan to the electrical wirin...

Page 10: ...fans WPA P N 04 06 2019 Infringement of the Section 3 Reservations of Producer of the Use and Maintenance Ma nual and especially modifications undertaken by User on one s own shall cause the loss of...

Page 11: ...ts Journal of Laws L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parlia ment and of the Council with regard to ecodesign requir...

Page 12: ...mawent com pl 805W10 WPA 3 P 1 N 04 06 2019 EN 805W21 WPA 3 P 3 N 04 06 2019 EN 805W11 WPA 5 P 1 N 04 06 2019 EN 805W12 WPA 5 P 3 N 04 06 2019 EN 805W13 WPA 6 P 1 N 04 06 2019 EN 805W14 WPA 6 P 3 N 04...

Reviews: