RADIAL  ROOF  FANS

  SMART-N 

 

 

D. 

Protect the housing from mechanical damage. 

E. 

Prior to installing, check the load

 capacity  of the constructional elements  where the fan will  

be 

mounted. Unsure installing could 

cause hazard to personnel / people in vicinity and effect 

in damage of the device. 

F. 

SMART-N fans  cannot be 

used for

 

conveying the air  contaminated with a mixture of 

flammable substances in form of gas, vapour, mist and dust, that in connection with 
the air could create the explosive atmosphere. 

G. 

Do not use the fans

  

for conveying the air containing viscous impurities that could ac-

cumulate on the device surface, especially on the impeller. 

H. 

Neither 

use 

them

 for forwarding the air with aggressive pollutants which will destruc- 

tively effect the device structure. 

I. 

During operation, the maximum impeller rotations should not exceed the nominal rotations. 

J. 

Producer is

 not responsible for wounds, injuries, body 

laceration experienced by User

 or per-

sonnel during the improper operational use. 

 

4.

 

Technical Data 

Table No.1 

Type of the fan 

 

Synchronous 

rotations 

Supply 

voltage 

Motor 

rate 

Maximum 

volume flow 

Maximum  

fan pressure 

Weight 

 

[r.p.m.] 

[V / Hz] 

[kW] 

[m³/h] 

[Pa] 

    [kg] 

SMART-160/3000-N         3000 

3 x 400 / 50    0,55         2300 

         820 

    20 

SMART-200/3000-N         3000 

3 x 400 / 50 

   0,55         2800 

         820 

    20 

SMART-200/1500-N         1500 

   0,55         2800 

         710 

    40 

SMART-200/1000-N         1000 

   0,37         2100 

         345 

    40 

SMART-250/3000-N         3000 

3 x 400 / 50 

   0,55         2900 

         520 

    20 

SMART-250/1500-N        1500 

   1,1 

       4600 

         790 

    44 

SMART-250/1000-N        1000 

   0,37         3160 

         370 

    42 

SMART-315/3000-N        3000 

3 x 400 / 50    0,55         3400 

         520 

    20 

SMART-315/1500-N        1500 

3 x 400 / 50    1,5 

       7800 

         890 

    60 

SMART-315/1000-N        1000 

3 x 400 / 50    0,55         5000 

         390 

    55 

SMART-400/1500-N        1500 

3 x 400 / 50    3,0 

     11100 

       1000 

    70 

SMART-400/1000-N       1000 

3 x 400 / 50    0,75         7000 

         400 

    59 

SMART-400/750-N 

       750 

3 x 400 / 50    0,37         5200 

         240 

    58 

SMART-500/1000-N       1000 

3 x 400 / 50 

   2,2 

     14900 

         530 

    94 

SMART-500/750-N 

       750 

   1,1 

     10700 

         290 

    87 

SMART-630/1000-N       1000 

3 x 400 / 50 

   4,0 

     22500 

         670 

  163 

SMART-630/750-N 

       750 

   2,2 

     18100 

         390 

  151 

SMART-710/1000-N       1000 

3 x 400 / 50 

   5,5 

     31000 

         740 

  174 

SMART-710/750-N 

       750 

   2,2 

     20500 

         390 

  155 

Caution: 

1. 

Ingress protection  

IP54

 

 

2. 

In order to reduce the noise level,  it is recommended to apply sound absorbing 

 

 

roof bases 

– type 

TPD-N

 and 

TPDC-N

 

 
 

 

Summary of Contents for SMART-160/3000-N

Page 1: ...812W70 SMART 400 750 N 31 05 2019 EN 812W61 SMART 200 1000 N 31 05 2019 EN 812W71 SMART 400 1000 N 31 05 2019 EN 812W62 SMART 200 1500 N 31 05 2019 EN 812W72 SMART 400 1500 N 31 05 2019 EN 812W63 SMA...

Page 2: ...of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parliament and of the Council with regard to ecodesign requirements for fans driven by motors with an electric input power...

Page 3: ...ional use 4 Technical Data Table No 1 Type of the fan Synchronous rotations Supply voltage Motor rate Maximum volume flow Maximum fan pressure Weight r p m V Hz kW m h Pa kg SMART 160 3000 N 3000 3 x...

Page 4: ...2019 Flow charts Table No 2 SMART 160 3000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 79 69 62 59 71 Table No 3 SMART 200 1000 N Acoustic pressure level dB A outlet inlet 1 m 5...

Page 5: ...sure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 79 69 62 59 71 Table No 4 SMART 250 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 65 56 48 44 53 SMART 250 1500 N Acoustic p...

Page 6: ...oustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 68 59 51 48 59 SMART 315 1500 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 80 70 63 60 70 SMART 315 3000 N Acoustic p...

Page 7: ...ustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 63 55 46 43 53 SMART 400 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 73 62 56 52 62 SMART 400 1500 N Acoustic pr...

Page 8: ...MART N 31 05 2019 Table No 7 SMART 500 750 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 69 59 52 49 61 SMART 500 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m...

Page 9: ...ROOF FANS SMART N Table No 8 SMART 630 750 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 77 67 60 56 70 SMART 630 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m...

Page 10: ...a motor with a radial impeller Impeller is statically and dynamically balanced according to ISO 14694 2003 AMD1 2010 gaining the G 2 5 class Lower skeletons of the 3000 r p m synchronous rotation fans...

Page 11: ...fans of 3000 r p m Fig No 1 Fans of SMART N types structure and dimensions Table No 10 Dimensions of the fans type SMART N except for fans of rotational speed 3000 r p m Type of the fan A B C D E Qua...

Page 12: ...on a roof of the industrial building it is important to install it on a pedestal with a suitable roof base It is recommended to apply the TPD N or TPDC N sound absorbing roof bases delivery on separat...

Page 13: ...and positioned at the place of operation Connection flange Fig No 3 Connection flange of the fan dimensions Table No 12 Dimensions of the connection flanges Type of the fan Connection flange A mm B mm...

Page 14: ...C 160 N 160 430 630 625 SMART 200 N TPDC 200 N 200 430 630 625 SMART 250 N TPDC 250 N 250 530 730 950 SMART 315 N TPDC 315 N 315 530 730 950 SMART 400 N TPDC 400 N 400 790 990 1200 SMART 500 N TPDC 50...

Page 15: ...the fan even for a check before the hood is reinstalled CAUTION 1 Insulation class I 2 Ingress protection IP54 3 Setting of the motor protective switch Q1 It 1 1 x In where In means rated current o th...

Page 16: ...egular periods of time i e once a year During the check take into account the function of the fan as well as its technical state All the activities connected with technical revisions on the fan have t...

Page 17: ...t be neither thrown nor knocked down Do not put any additional load on the device It is inadmissible to put one device on top of another no stacking During the transport protect them from atmospheric...

Page 18: ...s Journal of Laws L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parlia ment and of the Council with regard to ecodesign require...

Page 19: ...19 31 05 2019 RADIAL ROOF FANS SMART N NOTES...

Page 20: ...20 RADIAL ROOF FANS SMART N 31 05 2019 NOTES...

Reviews: