background image

Installation Manual

Installation

a. The sounder is installed by first mounting the base unit and making the

external wring connections to the base. The head unit then automatically

connects when it is attached to the base.

b. The sounder head is separated from the base by unlocking the four

¼-turn fasteners in the corners of the sounder.
(Recommended screwdriver: Philips No. 2, min 100mm long).

c. Note that the head only fits onto the base one way around. If a beacon

is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached

Wiring

The sounder and beacon have separate wiring terminals. Each terminal is
duplicated to enable simple ‘daisy-chain’ connection of multiple units.

Controls

a. Tone Selection

The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.

b. Volume Control

The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.

c. Beacon Flash Controls (If fitted)

The flash mode of the beacon can be altered using the 2-way
dipswitch marked

EN

Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)

Line

Terminal Marking

+
-
S2
S3
+
-

XENON BEACON

LED BEACON

Technical Specification:

Supply Voltage Range

10-60V DC

Current – Sounder

8-40mA* (Typ. 30mA @ 24V, Tone 1)

Current –Beacon

Xenon - 250mA Average, 700mA Peak*,

(Where fitted)

LED - 18mA (Flashing) or 65mA (Static)*

Peak Sound Level

100-113 dBA at 1m*

(Typ. 105dBA @ 24V, Tone 1)

Number of Tones

64

Volume Control

20dBA typical

Remote Tone Switching

Provision for 3 alarm stages

(Negative voltage activation)

Operating Temperature

-25°C to +70°C

Casing

High Impact Polycarbonate/ABS

IP Rating

IP66

Synchronisation

Automatic with Klaxon Nexus and

Sonos Sounders

*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.

The European directive “Waste Electrical and Electronic Equipment” (WEEE)
aims to minimise the impact of electrical and electronic equipment waste on
the environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return
end-of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.

From Controller

1st Stage

2nd Stage
3rd Stage

Sounder

Beacon

+

-

+

-

1st Unit

2nd Unit

To Next Unit

Nexus 105 DC Sounder & Sounder-Beacon

Installation Instructions

Switch

Off

On

Off

On

1

60 flashes per min 30 flashes per min Single Flash Double Flash

2

Single Flash

Double Flash

Flashing

Static

Summary of Contents for Nexus 105 DC

Page 1: ... I I O 1 106 25 24 250Hz 1200Hz 12Hz O I O I I I 1 101 23 25 500Hz 1200Hz 0 33Hz O I I O O O 1 108 21 26 2400Hz 2900Hz 9Hz O I I O O I 1 113 39 27 2400Hz 2900Hz 3Hz O I I O I O 1 111 39 28 800Hz 970Hz 100Hz O I I O I I 1 104 23 29 800Hz 970Hz 9Hz O I I I O O 1 104 27 30 800Hz 970Hz 3Hz O I I I O I 1 105 28 31 800Hz 0 25s ON 1s OFF O I I I I O 1 103 8 32 500Hz 1200Hz 3 75s 0 25s OFF AS2220 O I I I ...

Page 2: ...te 3rd Stage Alarm Control Connect to 0V to activate Beacon Positive Supply 10 to 60V DC Beacon Negative Supply 0V Line Terminal Marking S2 S3 XENON BEACON LED BEACON Technical Specification Supply Voltage Range 10 60V DC Current Sounder 8 40mA Typ 30mA 24V Tone 1 Current Beacon Xenon 250mA Average 700mA Peak Where fitted LED 18mA Flashing or 65mA Static Peak Sound Level 100 113 dBA at 1m Typ 105d...

Page 3: ...tsschäden durch Elektro und Elektronik Altgeräte so gering wie möglich zu halten Um diese Richtlinie einzuhalten dürfen Elektrogeräte die mit diesem Symbol gekennzeichnet sind nicht in den öffentlichen europäischen Entsorgungssystemen entsorgt werden Europäische Benutzer von Elektrogeräten müssen ab sofort Altgeräte zur Entsorgung zurückgeben Nähere Informationen hierzu finden Sie auf der folgende...

Page 4: ...g a Toonselectie De eerste en tweede fase alarmtonen worden onafhankelijk ingesteld door gebruik van 6 weg dimschakelaars S1 en S2 De vereiste instellingen worden in de tabel op de ommezijde weergegeven De derde fase alarmtoon is preset als aanvulling de geselecteerde eerste fase toon zoals weergegeven op de tabel b Volumeregeling De geluidsuitvoer van het apparaat kan tot 20dBA verminderd worden ...