background image

EN54-3
Fire Alarm Device – Sounder
Type B: For indoor or outdoor use
18-980542/543/544/653/655/588/620/621/658/659/657
Technical Data: Document 18-186528

0832

07

0832-CPD-0615 (Sounder-LED Beacon)
0832-CPD-0616 (Sounder-Xenon Beacon)
0832-CPD-0617 (Sounder)

Nexus 105 DC Sounder & Sounder-Beacon

Installation Instructions

EN

Klaxon Signals Ltd, Oldham, OL4 1HW, UK

Phone +44 161 287 5555

Fax +44 161 287 5511

E-mail [email protected]

Issue 7 (January 2008) 18-186456

Copyright © Klaxon Signals Ltd

www.klaxonsignals.com

Tone

Tone Type

Tone Description / Application

Dip Switch

3rd Stage

Peak Sound

Sounder

(S1/S2)

Tone

Level (dBA@1m) Current (mA Avg)

1.

970Hz (BS5839-1:2002)

O-O-O-O-O-O

18

105

31

2.

800Hz/970Hz @ 2Hz (BS5839-1:2002)

O-O-O-O-O-I

1

105

28

3.

800Hz – 970Hz @ 1Hz (BS5839-1:2002)

O-O-O-O-I-O

1

104

25

4.

970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)

O-O-O-O-I-I

1

105

17

5.

970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)

O-O-O-I-O-O

1

105

27

6.

554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )

O-O-O-I-O-I

1

103

20

7.

500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000)

O-O-O-I-I-O

1

108

19

8.

420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)

O - O - O - I - I - I

1

102

10

9.

500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)

O-O-I-O-O-O

1

106

13

10.

550Hz/440Hz @ 0.5Hz

O-O-I-O-O-I

19

104

21

11.

970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)

O-O-I-O-I-O

1

105

13

12.

2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)

O - O - I - O - I - I

1

107

16

13.

1200Hz – 500Hz @ 1Hz (DIN 33 404)

O-O-I-I-O-O

1

109

22

14.

400Hz

O - O - I - I - O - I

18

101

16

15.

550Hz, 0.7s/1000Hz, 0.33s

O - O - I - I - I - O

1

105

25

16.

1500Hz – 2700Hz @ 3Hz (Vandal Alarm)

O - O - I - I - I - I

1

113

32

17.

Simulated Bell

O-I-O-O-O-O

1

107

18

18.

840Hz

O-I-O-O-O-I

1

110

26

19.

660Hz

O-I-O-O-I-O

10

102

25

20.

660Hz 1.8s ON/1.8s OFF

O - I - O - O - I - I

19

102

14

21.

660Hz 0.15s ON/0.15s OFF

O-I-O-I-O-O

19

102

14

22.

510Hz, 0.25s/ 610Hz, 0.25s

O - I - O - I - O - I

1

103

24

23.

800/1000Hz 0.5s each (1Hz)

O - I - O - I - I - O

1

106

25

24.

250Hz – 1200Hz @ 12Hz

O - I - O - I - I - I

1

101

23

25.

500Hz – 1200Hz @ 0.33Hz.

O-I-I-O-O-O

1

108

21

26.

2400Hz – 2900Hz @ 9Hz

O - I - I - O - O - I

1

113

39

27.

2400Hz – 2900Hz @ 3Hz

O - I - I - O - I - O

1

111

39

28.

800Hz – 970Hz @ 100Hz

O - I - I - O - I - I

1

104

23

29.

800Hz – 970Hz @ 9Hz

O - I - I - I - O - O

1

104

27

30.

800Hz – 970Hz @ 3Hz

O - I - I - I - O - I

1

105

28

31.

800Hz, 0.25s ON/1s OFF

O - I - I - I - I - O

1

103

8

32.

500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)

O - I - I - I - I - I

1

108

20

33.

340Hz

I-O-O-O-O-O

1

101

17

34.

1000Hz

I-O-O-O-O-I

18

106

25

35.

1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)

I-O-O-O-I-O

1

104

34

36.

660Hz 6.5s ON/13s OFF

I - O - O - O - I - I

19

102

9

37.

1000Hz/2000Hz, 1s each

I-O-O-I-O-O

1

108

25

38.

720Hz, 0.7s ON/0.3s OFF

I - O - O - I - O - I

1

104

16

39.

970Hz, 0.25s ON/OFF

I - O - O - I - I - O

1

105

17

40.

2800Hz, 1s ON/OFF

I - O - O - I - I - I

1

106

20

41.

2800Hz 0.25s ON/OFF

I-O-I-O-O-O

1

106

19

42.

2400/2900 @ 2Hz

I - O - I - O - O - I

1

113

38

43.

Chime, 554Hz/440Hz Single shot ‘ding dong’

I - O - I - O - I - O

1

100

15

44.

Chime, 554Hz/440Hz Repeating ‘ding dong’

I - O - I - O - I - I

1

102

15

45.

Chime, 970Hz/800Hz Single shot ‘ding dong’

I- O - I - I - O - O

1

101

36

46.

Chime, 970Hz/800Hz Repeating ‘ding dong’

I - O - I - I - O - I

1

100

36

47.

Hooter, Repeating

I - O - I - I - I - O

1

102

13

48.

Gentle alarm - Tone 2, rises slowly to full volume over 30s

I - O - I - I - I - I

1

105

28

49.

Time-Out Alarm – As Tone 2, cuts off after 10 mins

I-I-O-O-O-O

1

105

28

50.

Time-Out Alarm – As Tone 2, cuts off after 2 mins

I - I - O - O - O - I

1

105

28

51.

750Hz 0.33s ON/0.51s OFF

I - I - O - O - I - O

1

103

8

52.

750Hz 0.51s ON/0.33s OFF

I - I - O - O - I - I

1

103

15

53.

550Hz, 0.33s/1000Hz, 0.7s

I - I - O - I - O - O

1

106

25

54.

600Hz – 900Hz/ 0.9s

I - I - O - I - O - I

1

104

31

55.

660Hz – 680Hz/ 0.9s

I - I - O - I - I - O

1

101

28

56.

670Hz – 725Hz/ 0.9s

I - I - O - I - I - I

1

104

25

57.

920Hz – 750Hz/ 0.9s

I - I - I - O - O - O

1

104

30

58.

700Hz - 900Hz, 0.3s/0.6s OFF

I - I - I - O - O - I

1

104

11

59.

900Hz - 760Hz, 0.6s/0.3s OFF

I - I - I - O - I - O

1

105

19

60.

750Hz

I - I - I - O - I - I

18

103

22

61.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - O

43

62.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - I

43

63.

Power Only – Use with Stage 3 control for manual/intermittent horn triggering

I - I - I - I - I - O

47

64.

Reserved for future use

I - I - I - I - I - I

DE

FR

NL

ES

Summary of Contents for Nexus 105 DC

Page 1: ... I I O 1 106 25 24 250Hz 1200Hz 12Hz O I O I I I 1 101 23 25 500Hz 1200Hz 0 33Hz O I I O O O 1 108 21 26 2400Hz 2900Hz 9Hz O I I O O I 1 113 39 27 2400Hz 2900Hz 3Hz O I I O I O 1 111 39 28 800Hz 970Hz 100Hz O I I O I I 1 104 23 29 800Hz 970Hz 9Hz O I I I O O 1 104 27 30 800Hz 970Hz 3Hz O I I I O I 1 105 28 31 800Hz 0 25s ON 1s OFF O I I I I O 1 103 8 32 500Hz 1200Hz 3 75s 0 25s OFF AS2220 O I I I ...

Page 2: ...te 3rd Stage Alarm Control Connect to 0V to activate Beacon Positive Supply 10 to 60V DC Beacon Negative Supply 0V Line Terminal Marking S2 S3 XENON BEACON LED BEACON Technical Specification Supply Voltage Range 10 60V DC Current Sounder 8 40mA Typ 30mA 24V Tone 1 Current Beacon Xenon 250mA Average 700mA Peak Where fitted LED 18mA Flashing or 65mA Static Peak Sound Level 100 113 dBA at 1m Typ 105d...

Page 3: ...tsschäden durch Elektro und Elektronik Altgeräte so gering wie möglich zu halten Um diese Richtlinie einzuhalten dürfen Elektrogeräte die mit diesem Symbol gekennzeichnet sind nicht in den öffentlichen europäischen Entsorgungssystemen entsorgt werden Europäische Benutzer von Elektrogeräten müssen ab sofort Altgeräte zur Entsorgung zurückgeben Nähere Informationen hierzu finden Sie auf der folgende...

Page 4: ...g a Toonselectie De eerste en tweede fase alarmtonen worden onafhankelijk ingesteld door gebruik van 6 weg dimschakelaars S1 en S2 De vereiste instellingen worden in de tabel op de ommezijde weergegeven De derde fase alarmtoon is preset als aanvulling de geselecteerde eerste fase toon zoals weergegeven op de tabel b Volumeregeling De geluidsuitvoer van het apparaat kan tot 20dBA verminderd worden ...

Reviews: