 DC Input Rear Panel 
 

 

Picture shown MW1210 

 
 

Material Prepare for Installation 

Typical Wiring block diagram of the Power Inverter: 
 
 
 
 
 
 
 
 
 
 
 

12V Battery Bank: 

 

The use of deep cycle battery is highly recommended for power inverter application 

 

For battery size, you need to identify how much you will be using them between charges. 
KISAE do recommends you purchase as much battery capacity as possible. See more on 
Battery Run time and Load in Section 4. 
 

Fuse or Circuit Breaker:   

 

DC-rated fuse or DC-rated circuit breaker connected along the DC positive line is required. 

 

For MW 1210, SW 1210, select a fuse or circuit breaker with a minimum of 150 Adc 

 

For MW 1215, select a fuse or circuit breaker with a minimum of 225 Adc 

 

For SW 1220, select a fuse or circuit breaker with a minimum of 300 Adc 

 

Based on the size of the battery bank chosen on the 12V Battery Bank above, determine the 
overall short circuit current rating of the battery bank from the battery manufacturer. The fuse 
or circuit breaker chosen has to be able to withstand the short circuit current that may be 
generated by the battery bank. 
 

Disconnect Switch: 

 

Select a Disconnect Switch with the same or higher the rating of the selected fuse or circuit 
breaker from the above. 

 

The Disconnect Switch is used to disconnect the DC power between the power inverter and 
the battery bank during service, maintenance or trouble shooting. 

 
DC Input and Grounding Cable: 

 

Use of low resistance wire is required for all the DC connections between the inverter and the 
battery bank. 

 

For MW 1210, SW 1210, uses minimum #2 AWG wire with maximum cable length of 5 feet. 

 

For MW 1215, use minimum #1/0 AWG wire with maximum cable length of 5 feet. 

 

For SW 1215, use minimum #2/0 AWG wire with maximum cable length of 5 feet. 

Important: 

The unit is grounded through the ground stud of the unit located near the DC Input 

Fan 

opening 

 
 
 
DC Input Terminals 
 
 
Ground Terminal 

    Power Inverter 

(MW 1210, 

MW 1215, 

SW1210, 

SW 1220) 

Disconnect 

Switch 

Fuse or Circuit 

Breaker 

 
 

12 V Battery Bank 

 
(Charger system 
sold separately is 
required to charge 
the battery bank 
when battery is 
discharged) 
 

Pos + 

Neg - 

AC 

USB  

LOADS 

Summary of Contents for MW 1210

Page 1: ...Modified Sinewave Power Inverter 1000 1500 MW 1210 MW1215 True Sinewave Power Inverter 1000 2000 SW 1210 SW 1220 Owner s Manual Modified Sinewave Series True Sinewave Series ...

Page 2: ...cations and product functionality may change without notice Important Please be sure to read and save the entire manual before using your KISAE Power Inverter Misuse may result in damage to the unit and or cause harm or serious injury Read manual in its entirety before using the unit and save manual for future reference Product Numbers Modified Sinewave series MW 1210 Power Inverter 12V 1000W MW 1...

Page 3: ...Page 3 Table of Contents 1 INTRODUCTION 4 2 PRODUCT DESCRIPTION 5 3 INSTALLATION 5 4 UNIT OPERATION 9 5 TROUBLESHOOTING 10 6 SPECIFICATIONS 11 7 WARRANTY 12 ...

Page 4: ...follow all the battery manufacturer s specific precautions when installing using and servicing the battery connected to the inverter Wear eye protection and gloves Avoid touching your eyes while using this unit Keep fresh water and soap on hand in the event battery acid comes in contact with eyes If this occurs cleanse right away with soap and water for a minimum of 15 minutes and seek medical att...

Page 5: ...UCT DESCRIPTION The KISAE Power Inverter package includes the items list below Power Inverter base unit one of the following models MW 1210 Power Inverter 1000 Modified Sinewave MW 1215 Power Inverter 1500 Modified Sinewave SW 1210 Power Inverter 1000 True Sinewave SW 1220 Power Inverter 2000 True Sinewave Owner s manual P N MU MW1215 3 INSTALLATION WARNING KISAE Technology recommends that all wir...

Page 6: ...urer The fuse or circuit breaker chosen has to be able to withstand the short circuit current that may be generated by the battery bank Disconnect Switch Select a Disconnect Switch with the same or higher the rating of the selected fuse or circuit breaker from the above The Disconnect Switch is used to disconnect the DC power between the power inverter and the battery bank during service maintenan...

Page 7: ... For indoor use the orientation of the unit can be mounted in any direction except with the DC Input panel facing downwards For RV installation the unit has to be mounted flat on horizontal surface Use mounting template below to mark the positions of the mounting screws Drill the 4 mounting holes and place the inverter in position and fasten the inverter to the mounting surface Power Inverter Chas...

Page 8: ...lder Turn Disconnect Switch to ON position Remote Switch optional Connection Insert the Remote Switch to the RJ11 Remote Port located at the Front AC panel of the Power inverter Please note polarity Test the Power Inverter connection Turn unit on by pressing and holding the On Off button on the main unit for about a second until a beep sound occur The Status light turns on indicating the KISAE Pow...

Page 9: ... shutdown Please check error code to troubleshoot the unit Understanding the Error Code Code Condition Corrective Action E01 Unit has sensed input under voltage and has shutdown Recharge battery immediately and restart unit E02 Unit has sensed input over voltage and has shutdown Check battery voltage or if any external charger is connected to the battery bank E03 Unit output has sensed overload or...

Page 10: ...OOTING To trouble shoot the unit please note the error code display on the main unit and review the Understanding the Error Codes in section 4 Problem Symptom Solution No output voltage And Status LED is off The unit is off Turn unit ON by following the instruction in Section 4 to turn unit ON No power to inverter Check fuse or the Disconnect switch if installed is either blown or turn OFF No AC o...

Page 11: ... 5 VDC Under Voltage Recovery 11 8 VDC Over Voltage Shutdown 15 5 VDC USB 5V 750 mA Safety and Environmental Conformance Conforms to UL 458 Certified to CSA C22 2 no 107 1 Agency Markings cETLus Operating Temperature 0 C to 40 C 32 F to 104 F Storage Temperature 20 C to 60 C 4 F to 140 F Relative Humidity 5 90 noncondensing Operating Altitude Up to 9 843ft 3000 meters above sea level Weights and D...

Page 12: ...tail store After speaking to a customer service representative if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of original purchase Any defective unit that is returned to manufacturer within 30 days of the date of purchase will be replaced free of charge If such a unit is returned more than 30 days but less than one year from ...

Reviews: