background image

 

17 

tdo 

Time delay in deactivating the compressor once the door opens

 

and activate the door alarm

. Once the door 

closes, the compressor is activated and the alarm turns off. 

99 

min 

DEFROST 

18 

dFr 

Time between two successive defrost

, where if dFr = 0 or the relay is in heating mode, defrost is 

deactivated. 

50 

hours 

19 

dd2 

Defrost duration (manual and automatic) 

90 

18 

min 

20 

dE5 

Defrost end temperature - room temperature - terminals sensor 5-6 
The defrost shut-off temperature is the temperature of the room, regardless of whether we have connected 
the heat exchanger sensor. Above this room  temperature the automatic defrost stops. 
Manual defrosting starts regardless of the room temperature and is of duration dd2. 
In case of fault (LF1) of the room sensor, the end of defrost temperature is not checked and is completed 
after the selected time dd2.

 

25.0 

10.0 

°C/°F 

21 

dY4 

Display indication during defrost 

0 = room temperature is displayed 
1 to 40 minutes = “dFr” is displayed from 1 to 40 minutes from the initiation of defrost 

99 

20 

min 

22 

dP3 

Dripping time, where the compressor is OFF after defrost

 

10 

min 

23 

tdH 

Time delay in activating high temperature alarm "AHi" after defrost.  

The "AHi" alarm is not activated during defrost. 

99 

min 

SMART DEFROST (more details page 2) 

24 

dSE 

Smart defrost function 

0 = NO 
1 = YES

 

25 

dSb 

Starts a defrost cycle at the start of the device 

0 = NO 
1 = YES

 

26 

dS2 

Minimum time between two consecutive smart defrosts 

40 

255 

60 

min 

27 

dS1 

Time constants, the steadier the increase, the harder it is to start smart defrosting 

20 

min 

28 

dSt 

Temperature constant, the higher the constant, the harder it is to start smart defrosting 

0.5 

3.0 

1.0 

°C/°F 

COMPRESSOR 

29 

CP2 

Compressor’s minimum time OFF 

min 

30 

CF3 

Compressor’s  operation  in  case  of  room’s  sensor  malfunction  LF1 

and  in  cooling  mode,  the  compressor 

operates as follows

:  

0 = 40% ΟΝ compressor (3 minutes ΟΝ, 4 minutes OFF) / 1 = ΟΝ constantly the compressor.  
In heating mode with parallel sensor malfunction (LF1), the relay switches off. 

RELAY 

31 

rHC 

Relay operation mode, where 0 = cooling / 1 = heating / 2 = heating with countdown based on timer 

Hod

 

0=cooling 

32 

Ηοd 

Countdown timer when the relay is in heating mode with countdown, adjust also parameter 

rHC = 2 

255 

min 

NETWORK - GENERAL SETTINGS 

33 

Add 

Device address on network

 

255 

34 

trE 

Response time of the device on network 

100 

40 

msec 

35 

bAU 

Baud rate: 2 = 9600 

2=9600 

36 

Pro 

Cabinet’s program (factory settings) is displayed – no access 

1  

37 

tPE 

Unique product number – no access 

45 

 

ALARM TABLE 

LF1 

Room sensor malfunction 

LF2 

Evaporator sensor malfunction 

ΑLo 

Low room temperature 

ΑHi 

High room temperature 

dοr 

Open door alarm  

EEr 

RAM error: re-enter the SPo (see Setting the device temperature - SET POINT previous page)

 

The alarms are automatically deactivated once the cause of the alarm disappears. 

 
 
 
 
 
 
 
 
 
 
 
 

Made in Greece

.

 

 

 

The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician. 

The guarantee covers only the replacement or the service of the device. KIOUR PC implements a Quality Management System according to EN ISO 9001:2015 Standard with registration number 
01013192.

 

KIOUR preserves the right to adjust its products without further notice 

 
 

392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331  [email protected]  www.kiour.com

 

V1.0.151020

 

 

Reviews: