TEMPERATURE CONTROLLER TOUCH LINE Model RSD
Description
RSD is a temperature controller for refrigerator rooms using touch technology for the keyboard. Through a PTC sensor controls temperatures in range -50÷+150 °C (-58÷+302 °F).
In scale -19.9÷+99.9°C there is a decimal analysis with accuracy ±0.1°C. It has three relays (compressor, fan and level control), deFrost control and buzzer activation due to an
alarm.
Start up
At the startup of the device, the temperature controller performs a self-ckeck for 7 sec and the room temperature is displayed. Do not touch the screen during self-check. By pressing
the two arrows (
[
],[
] ) at the same time for 3 seconds the countdown starts and
the temperature controller unlocks
(images below)
. By pressing
[
] for 3sec we turn ON or
turn OFF the controller (images below)
. The keyboard locks automatically after 50sec without activity.
Indications and buttons
indication
function
compressor
fan
deFrost
locked keyboard
water evaporation
resistance is ON
sensor’s alarm
button
function
enter
down arrow
ΟΝ/ΟFF
mute buzzer
up arrow
Set
manual deFrost
Technical specifications
Power supply: 230VAC 50/60Hz
Maximum power consumption: 3W
PTC temperature sensor
Accuracy: 0.1% ± 1 digit
Buzzer alarm
Serial Input
Relay 250VAC 30A resistive load 2HP
Relay water level and ON/OFF
250VAC 10A
Operating temperature: -15÷+55°C
Storage temperature: -20÷+80°C
The device is mounted through panel hole
29x71mm.
Connection with contacts 6.3mm
Functions of the buttons
button
operation
pressed once
pressed more than 3 sec
enter parameters menu
confirm new value
-
indicate temperature range °C/°F
mute buzzer in case of an alarm
ON/OFF controller
-
-
cancel new value
manual deFrost
Managing the parameters
By pressing [
] we enter the parameter’s menu.
The first parameter SPo is displayed and with the
[
], [
]
we scroll into the parameters with the order they
appear to the parameters table below.
By pressing [
] the value of the parameter is displayed and with the
[
], [
]
we change the value.
By pressing [
] we confirm the new value and the name of the parameter is displayed.
By pressing [
] we cancel the new value and the name of the parameter is displayed.
By pressing [
] we exit the parameters menu.
Connections
Serial input
RSD can connect to the key programmer or the data logger Mini Logger or the CAMIN network or to an external device for exporting alarms. From the parameters UF
and Add we can adjust the serial input.
Key programmer: controller’s parameter values can be saved or retrieved from the programming key. Connect the programming key to the controller and by pressing
[
] and
[
]
the device connects with the key and the message Eo is displayed.
By pressing
[
]
the device reads the parameters from the key and the message ro = read O.K. or rF = read Fail is displayed.
By pressing
[
]
the device writes the parameters to the key and the message Yo = Write O.K. or YF = Write Fail is displayed.
In case of failure (rF or YF) reenter the key to the serial input and repeat the procedure from the beginning. The key can connect to all
devices. If you try to
read the parameters of a different device, message rF is displayed. At any time we can perform the aforesaid operation. After 10 sec the key is disconnected.
Data logger Mini Logger: the controller can connect to the data logger and save its temperatures based on selected minutes, its status and alarms to a microSD
memory card. It connects to the controller via a cable and the parameter Add = 1 must be adjusted.
CAMIN PC network: the controller can connect to CAMIN network (RS485, modbus protocol) through an interface NET-IN-1. CAMIN is an application designed to
collect information, watch and fully control a net of devices. The maximum length of the net can be 1000 meters
.
Parameters table
No
parameter
min
max
def
UOM
1
SΡo
SET POINT: temperature control room
ALo
AHi
0.0
°C/°F
2
ALo
lower alarm limit temperature of the room
-50
AHi
-4.0
°C/°F
3
AΗi
higher alarm limit temperature of the room
Alo
+150
12.0
°C/°F
4
dFr
deFrost repetition time every 24h
0
12
6
-
5
Cod
code to enter parameter’s menu = “22"
0
255
0
6
diF
differential operating temperature of SPo
0.1
25.0
3.0
°C/°F
7
CFA
In case of sensor’s malfunction (LF1),the compressor
operates as follows:
0 = 40% compressor’s operation (3min ΟΝ, 4min OFF),
1 = 100% compressor’s operation (ΟΝ continuously).
0
1
0
-
8
Crt
minimum pause time of the compressor
0
4
2
min
9
dti
maximum duration of deFrost
1
90
12
min
10
dLΕ
Temperature limit of deFrost: above this temperature
the automatic deFrost stops and it is not possible to start
the procedure again manually. Manual deFrost lasts 20
min and does not stop based on “dL” temperature limit.
0.0
25.5
10.0
°C/°F
11
doP
type of deFrost: compressor OFF (not programmable)
-
-
-
-
12
dri
dripping time, in which the compressor remains OFF after
deFrost ends
0
10
0
min
13
tdF
During deFrost the indication “dF” is displayed, where “0”
= the room’s temperature is displayed during defrost.
0
99
20
min
14
ΑJ1
zero adjustment of temperature sensor
-9.9
+15.5
0.0
°C/°F
15
ΑJ2
out of order
16
tSd
time delay for refreshing the temperature indication on
screen
0
20
0
sec
17
F_C
switch °C/°F (0=°C, 1=°F) ATTENTION: changes
between °C/°F do not apply on SPo
0
1
0
°C/°F
18
brA
baud rate (9600mbps)
-
-
-
-
19
trE
time response of the device to the CAMIN network
5
100
20
msec
20
FFu
Relay ON-OFF operation (1=ON continuously, 0=ON when the
compressor is ON)
0
1
1
-
21
UFu
serial input operating mode, where 0 = operates with the
network and the serial key,1 = connects with an external
device for exporting alarms, ATTENTION: if the value in
“Add” parameter is ≠ 0, then the “Uf” is programmed
automatically to 0.
0
1
0
-
22
SLo
minimum temperature limit of SPo
-50
SHi
-2.0
°C/°F
23
SΗi
maximum temperature limit of SPo`
SLo
+150
+8.0
°C/°F
24
Odo
Door input polarity (0=OFF, 1=ON with ΝΟ contact,
2=ΟΝ with NC contact). When the door opens, the fan
turns OFF immediately.
0
2
2
-
25
At2
Start delay time alarm, where:
0 = activate immediately,
1 ÷ 120 min = the alarm is activated after the selected minutes.
For sensor and door failure alarms, the above rules do not apply.
-1
120
20
sec
26
U3
out of order
-
-
-
-
27
U4
out of order
-
-
-
-
28
U5
out of order
-
-
-
-
29
Add
address of the device in the CAMIN network
0
255
0
-
Alarm’s Table
1
LF1
sensor’s malfunction
2
ΑLo
low temperature in the room
3
AΗi
high temperature in the room
4
dοr
open door
ATTENTION to prevent electrostatic discharges at the side slots of the device and sharp objects from been inserted.
ATTENTION: separate the signal's cables from the power supply's cables to prevent electromagnetic disorders
Signal
cables must never be in the same pipe with the power supply cables.
Read and keep these instructions. The device is under two year's guarantee of good operation. The guarantee is valid only if the manual instructions have been
applied. The control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or
the service of the device.
Rev1.3.250216
preserves the right to adjust its products without further notice.
MADE IN GREECE
When the door opens, the "dor" alarm is activated automatically after 2 min. If the door remains open for more than 4min, the
compressor automatically turns off. When an alarm appears, the buzzer is activated. By pressing
[
]
we mute the buzzer,
while the alarm continues to be displayed until the malfunction is restored.
T2
T2