background image

 

 

  

Kingspan  

SHE Control Panel TRZ Plus 2A 

and TRZ Plus Comfort

 

Technical Manual

Compact Control Panel 2A and Compact Control Panel 2A/M

Light + Air 

UK & Republic of Ireland

Summary of Contents for Compact Control Panel 2A

Page 1: ...Kingspan SHE Control Panel TRZ Plus 2A and TRZ Plus Comfort Technical Manual Compact Control Panel 2A and Compact Control Panel 2A M Light Air UK Republic of Ireland ...

Page 2: ...ch 14 Connecting Diagram SHE manual Call Point 15 Connecting Diagram Smoke Detector 16 Connecting Diagram Fire Alarm System 17 Connecting Buzzer Signal Lamp 18 Connecting Diagram Wind Rain Detector 19 Connecting Diagram Potential Free Contacts 19 Connecting Selector Switch Manual Automatic Temperature Sensor and Vent Switch 20 Connecting Multisensor for Measurement of Humidity CO2 Quality ppm and ...

Page 3: ...on alarm Separately fused power input 230V AC 50 Hz Hinged door or cover lockable Conforms to current state of the art standards Processor controlled Versatile connection facilities Service port interface included TÜV type tested Tested according to EN 12101 10 Scope of Delivery 1 x SHE control panel 1 x rechargeable batteries 2 x velcro tapes for fastening the batteries Compact Control panel 2A 2...

Page 4: ...nted Operation Safe operation is guaranteed if the acceptable rated values and guidelines regarding maintenance information stated in this documentation as well as supplementary information provided by the manufacturer are followed Malfunction If a malfunction is identified in the course of installation maintenance inspection etc immediate action should be taken to rectify the problem Repair and m...

Page 5: ...e burglary and attack alarm systems If necessary cable types must be defined in conjunction with the local approval bodies power supply companies or fire safety authorities Cabling for extra low voltages e g 24V DC is to be laid separately from low voltage line e g 230V AC Flexible cables must be laid in such a way that they cannot be sheared off twisted or snapped during operation Power supplies ...

Page 6: ... must be routed separately from the mains supply lead When routing the cables please observe the corresponding VDE regulations with expansion via additional printed circuit board TRZ WRMAS Basic by TRZ Plus Comfort Seren 24 V AC DC 100 mA Cable type see chapter cable length diagram Protective conductor cable may NOT be used Observe VDE regulations Either magnetic locking 24 V DC or linear drives j...

Page 7: ...If automatic detectors are connected only Smoke heat extraction opening windows Smoke reaches the automatic detectors the windows are opened completely the red display in the automatic detector is shining the red LED display SHE activated is shining at all SHE manual call points the ventilation function is out of order Smoke heat extraction closing windows Press the switch Closed at a SHE manual c...

Page 8: ...ay or there is no ventilation button in the door of the TRZ Plus Comfort the stroke limit setting must be made through the optional service port software Note In case of mains or battery failure or SHE activation the function is out of order In case of mains or battery failure the windows close immediately LED Display In the SHE control panel and SHE manual call points The green LED display OK ope...

Page 9: ... factor made up from 2 5V max permissible voltage drop and electrical conductivity of copper ggf Aufschlagin xL m 73 adingfactorin xL m 73 A mm I A x L m 73 M M simple cabel length L Notes re selection of cables For the motor supply cables of SHE drives 3 or 5 duplicated layout individual cores are required Two cores 4 cores are for the motor voltage the 3rd or 5th core respectively is required fo...

Page 10: ... e g type WRM 24V WRM2 or 1 rain detector e g RM RM2 Only with TRZ Plus Comfort or with additional module WRMAS in each case one connection for potential free report SHE activated NO normally Open contact and malfunction NC normally closed contact 24V max 0 5 A Only with TRZ Plus Comfort or with additional module WRMAS Fuse F2 Motor Switch SHE Closed Reset DIP Switch PC Service Port Fuse battery B...

Page 11: ...ction No SHE and no malfunction detection green LED OK operating is shining Activate SHE The closing contact at the terminals 4 5 switches The function is OK if the passage can be measured Activate SHE Closed initial position no SHE activation and no malfunction detection Take off the battery fuse F3 to simulate a malfunction Activation Replace fuse F3 back control panel again in initial position ...

Page 12: ...g diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel or of the external components The notes and installation directives in the technical documentation are always to be observed Provide a separately disengageable circuit Secure against unintentional switching off several drives per motor circ...

Page 13: ...lour mix ups can lead to incorrect function of the control panel or of the external components The notes and installation directives in the technical documentation are always to be observed Connecting Diagram Magnetic Clamps Magnetic Locking Magnetic locking one magnetic clamp magnetic locking Magnetic clamp Magnetic locking Magnetic clamp several magnetic clamps magnetic lockings Junction box Jun...

Page 14: ...s connected Route the connecting cables into the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel or of the external components The notes and installation directives in the technical documentation are alw...

Page 15: ...6 1 OK 10kΩ RBH 3A OK RBH 3A RBH 3A All work to be carried out without mains supply 230V AC or any batteries connected Route the connecting cables into the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel...

Page 16: ...el or of the external components The notes and installation directives in the technical documentation are always to be observed without smoke detector one smoke detector SSD 521 UTD 521 UTD 523 MSD 523 last smoke detector several smoke detectors SSD 521 UTD 521 UTD 523 MSD 523 one smoke detector last smoke detector last smoke detector 1 smoke detector 18 19 10kΩ 18 19 1 2 3 4 5 6 1 2 3 4 5 6 10kΩ ...

Page 17: ...es into the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel or of the external components The notes and installation directives in the technical documentation are always to be observed without fire alarm...

Page 18: ...o the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel or of the external components The notes and installation directives in the technical documentation are always to be observed with alarm buzzer with a...

Page 19: ...ied out without mains supply 230V AC or any batteries connected Route the connecting cables into the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrected connections or figure or colour mix ups can lead to incorrect function of the control panel or of the external components The notes and installa...

Page 20: ...ical documentation are always to be observed Variant 1 with two temperature sensors Adjustable hysteresis for opening and closing of windows over the respective temperature sensor The farther apart the temperature values the less unwanted movement commands from the window operators are short term temperature changes for example Drafts made STOP 4 3 2 1 8 11 10 9 20 C 18 C á á S P Ö S P Ö H A 3 4 4...

Page 21: ...connections for the power supply of the multisensor Notes to the DIP switches are observed Are an external buzzer or flashing light connected to signal an SHE message to these terminals the energy supply of the terminals to the additional board WRMAS is apparent see Option 2 20 21 11 10 8 MS 6 á á S P Ö S P Ö 24 V DC GND Ensure jumper position open close Variant 2 Energy supply for the multisensor...

Page 22: ... Connection Diagram All work to be carried out without mains supply 230V AC or any batteries connected Route the connecting cables into the control panel housing at the top Connect all connecting cables according to the wiring diagram and make sure that they are correctly connected Incorrect connections or figure or colour mix ups can lead to incorrect function of the control panel or of the exter...

Page 23: ... 230 V AC and without accumulator attached Factory settings for the DIP Switch are position OFF Position ON means DIP Switch 1 Motor timing device is switched off in SHE for 30 min VdS function DIP Switch 2 Motor output permanently switched on for operation with magnetic clamps to reinforce the locking force of the drives sealed closure of windows Battery is not buffered Switched off in the factor...

Page 24: ...ch 8 ON additionally via Close button of an SHE manual calling point DIP Switch 5 Pre alert A malfunction signal will take place if an automatic detector releases if more than one automatic detector releases SHE release will take place DIP Switch 6 Actuation limit Time dependent ventilation actuation limit For adjustment see section on Functional description actuation limit DIP Switch 7 Malfunctio...

Page 25: ...Operating mode SHE and ventilation without stroke limit DIP Switch 2 3 ON Combination with DIP Switch 4 5 7 12 still possible Function Shut in direction Closed e g push button closing malfunction takes 3 minutes time until unlocking the motor exits Note The ventilation command close has to be preformed for at least 3 minutes before start up procedure DIP Switches activation When the settings of th...

Page 26: ...onnection not OK Red LED lit up Press SHE Reset switch in the control panel Yellow LED is flashing check corresponding fuses see also beep code chart page 57 cable breakage check cable connections check if end module is missing in last smoke detector Ferritkern Battery lead Vent switches Press vent switch Open briefly the drives open the windows completely up to end position The display ventilatio...

Page 27: ...ter max 100 sec The yellow LED malfunction flashes In case of power failure the windows close immediately Press the Open switch of the vent switch no window reaction Press the switch SHE Open the windows open The red LED SHE activation is shining The green LED OK operating OK not lit up Press the switch Closed of the SHE manual call point the windows close completely The red LED SHE activation goe...

Page 28: ... will still remain Completion work Insert the glass panes in all SHE manual call points Close the control panel door Stick on the service contact telephone number Attention If the trial run fails repeat the initial start up procedure Troubleshooting Display operating OK is not shining in the SHE manual call points and the control panel a malfunction has occurred see malfunction beep code chart pag...

Page 29: ...el to secure the door Malfunction beep code chart The pulse sequence gives information regarding the source of the malfunction The continuous acoustical signal rings out only by SHE man call point with buzzer and if the door contact switch is pressed Note The yellow LED malfunction the red LED SHE activation and the green LED OK operating OK lits up permanently during the memory checks Maintenance...

Page 30: ...o this purpose we recommend a service contract with the manufacturer or another authorized specialist All standard batteries provided with the SHE control panel require regular checks as part of the maintenance programme and are to be replaced after the specified service life 4 years Observe the legal requirements when disposing of hazardous materials e g batteries Reset of the maintenance timer i...

Page 31: ...gspan SHE Control Panel TRZ Plus 2A and TRZ Plus Comfort 12 24999513 Dimensional drawing TRZ Plus 2A and TRZ Plus Comfort SMOKE VENT SMOKE VENT STOP 119 mm 195 mm 142 mm 146 mm 80 mm 83 mm TRZ Plus Comfort TRZ Plus 2A 215 mm ...

Page 32: ...ts and the vent switches must be well visible and accessible SHE call point 1 4 m over the top edge of the floor Do not assemble behind wall projections door casements or hide behind construction elements Open the SHE control panel and fix it at the specified bore holes to the construction body Make sure to provide appropriate material for the fixations Assembly of control elements drives junction...

Page 33: ...e No overhead installation or rotated by 180 mounting The control system must not be hidden by wall projections doors or structures Assembly Once the housing has been fastened to the wall 1 Insert ventilation plug on the underside of the housing Note Operating the control system without the ventilation plug can lead to malfunction and is not permitted Take care that the ventilation plug is not cov...

Page 34: ... the housing has been fastened to the wall 1 Thread velcro tapes for attaching the rechargeable batteries into the assembly panel Attention Start up procedure of the control panel only with installed plexiglass cover Note The Control panel is also available with a UP mounting kit Inserting the rechargeable batteries 1 With the help of the velcro tapes C in the bottom part of the baseplate fasten t...

Page 35: ...ected to mains voltage during configuration From version 01 04 00 onwards the control panel type TRZ Plus or Compact control panel 2A can be configured via the Service Port Software After starting the Service Port Software and clicking the Search button the configuration screen is automatically launched This interface is also used for the configuration of the compact control panel 2A and 2A M The ...

Page 36: ...usted manually After using the vent switch operation the drive closes according to the adjustment If vent switch operation is interrupted this function is deactivated and is not reactivated until opened again using the vent switch button operation Note This function is deactivated when supplied 2 2 Maximum opening using ventilation function This function is used to set up stroke limitation by run ...

Page 37: ...e Port Software After entering the password you get into the user interface of the service counter Here the maintenance counter is disabled or enabled Through the user interface maintenance counter any time can be chosen to signal a maintenance due The overdue maintenance is then displayed on the flashing green power LED Functions are not interrupted The maintenance counter is only active when the...

Page 38: ...c according to EN 12101 10 maximum current output 2A switched off at the primary energy source Charging time 24 h for emergency power Terminal max 1 5 mm 4 8 blade terminal with insulating bush 200 mm long Monitoring yes cyclical total discharge prot Fuse F3 battery FKS 5A Output Voltage Drives Magnetic clamps 27 V DC nominal 25 10 power Pmax 54W Pmin 0W Ripple Drives Magnetic clamps 1 Power nomin...

Page 39: ...s failure no ventilation blocked Safety functions in the event of mains failure yes automatic closure of the windows ventilation blocked while SHE continues to be active further functions via DIP Switches Maintenance Battery replacement every 4 years and in the event of battery malfunction Maintenance counter yes adjustable via PC Service Port Software Maintenance counter active when power is supp...

Page 40: ...er max 100 mA 100 ED Terminal max 1 mm screw terminal Cable monitoring function no max Pieces 1 Type WRM RM WRM2 RM2 Emergency power no Fuse no Free transmission SHE activation Closing contact max 30 V DC 0 5 amp collect Malfunction Opening contact max 30 V DC 0 5 amp When dimensioning the power supply and the cable cross sections for the supply lines to the motors as a function of the drive used ...

Page 41: ...cts or methods of working are for information only and Kingspan Limited and its subsidiaries accept no liability in respect thereof 07 2019 UK Kingspan Light Air Mellyn Mair Business Centre Lamby Industrial Park Wentloog Avenue Cardiff CF3 2EX T 44 0 29 2077 6160 Kingspan Light Air North East of England Business Centre Wearfield Enterprise Park Sunderland SR5 2TA T 44 0 191 5166253 E info kingspan...

Reviews: