28
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Start Up Procedure and Trial Run
Test Wind/Rain detector or rain sensor
(TRZ Plus Comfort)
Press Open switch in the vent switch, the windows open
completely, as long as no wind or rain alarm is pending.
Moisten the sensor surface of the rain detector with water,
the windows close completely. Display ventilation “Open”
flashes. Dry the rain sensor surface. Press Open switch in the
vent switch, the windows open completely.
Activate the wind detector with wind (e.g. hair dryer).
The windows close completely. Display ventilation “Open”
flashes.
Test buzzer / signal light
Press red “Open”-switch
in an SHE manual call point,
windows and the attached horn or signal light will be
activated.
The windows will open completely, red LED-indication
. - SHE released - will glow in all SHE manual call points, the
ventilation function is inoperative. Activation of the horn /
signal light will be cancelled after 3 min SHE release will still
remain.
Completion work
Insert the glass panes in all SHE manual call points. Close the
control panel door. Stick on the service contact telephone
number.
Attention:
If the trial run fails, repeat the initial start
up procedure!
Troubleshooting
Display - operating OK - is not shining
in the SHE manual
call points and the control panel:
• a malfunction has occurred (see malfunction beep code
chart, page 19), eliminate the malfunction.
• mains power connection out of order:
- check mains supply lead / voltage.
- check mains fuse.
• batteries out of order:
- check battery fuse.
- check battery connection.
- defective batteries, to be replaced.
The drives open without pressing a switch
• SHE manual call point incorrectly connected or defective,
check and correct.
• automatic smoke detector soiled, replace.
• due to a fault vent switch in permanent contact.
Vent switch with reversed function
• reverse connection at the vent switch or in the control
panel.
Vent switch without function
• Vent switch incorrectly connected.
• SHE activated, press Reset switch in the control panel.
• No voltage to mains supply lead, repair.
• Mains fuse defective, replace.
• Motor fuse defective, replace.
• Wind/rain alarm pending (additional module only).