19
Before proceeding to the connection of the
oven make sure that:
- the limiting valve and the domestic
electrical circuit are sufficient to support
the load of the appliance (see
identification plate);
- the electrical system is equipped with
an earthing cable in accordance with
current norms and legal provisions;
- the plug or omnipolar switch used to carry
out the connection is easily accessible
once the appliance is installed.
The appliance is sold with power cable, the
conductors of which have a minimum section
of 3x1.5 mm. Besides this, the cable must
have a normalised plug suitable for the
electrical load indicated on the identification
plate.
The plug should be connected to a suitable
elctrical socket.
If a direct connection to the supply is desired
an omnipolar switch having a minimum
opening of 3mm between the contacts must
be installed between the appliance and the
electricity supply; this switch must be
suitable for the electrical load of the
appliance and must conform to the current
norms.
The yellow/green earth wire must not be
interrupted by the switch.
In every case the supply cable must be
positioned insuch a way that it can, at no
time, reach temperaures of more than 90°C.
After connection test the heating elements
by putting them into operation for abour 3
minutes.
The manufacturers decline all
responsibility for damage or
accidents in cases where norms
have not been observed and
respected.
Electrical connection
Only qualified personnel should install the appliance (place in cabinet and make
electrical connection). Every operation must be carried out with appliance
disconnected from the electricity supply; when this is not possible the maximum
care is required when working on the appliance.