Page 44 of 57
King Pigeon Hi-Tech. Co., Ltd.
Ver 3.0
GSM/SMS/GPRS/3G/4G
Cellular IoT M2M RTU
30
TU DIN2 Count
Value
32 Bit Unsigned
This value Enable when DIN0 as
counter mode
32
TU DIN3 Count
Value
32 Bit Unsigned
This value Enable when DIN0 as
counter mode
Read and Write Holding Coil (Function Code 1, Function Code 5, Function Code 15.)
Register Address
(Decimal)
Definition
Data Type
Description
0
RTU DO0
Bool
DO0 Value, Read/Write, 1=Close, 0=Open
1
RTU DO1
Bool
DO1 Value, Read/Write, 1=Close, 0=Open
2
RTU DO2
Bool
DO2 Value, Read/Write, 1=Close, 0=Open
3
RTU DO3
Bool
DO3 Value, Read/Write, 1=Close, 0=Open
Read and Write Holding Coil (Function Code 03, Function Code 06, Function Code 16.)
Register Address
(Decimal)
Definition
Data Type
Description
260(bit0)
DI0 Count clear bit
Bool
Write 1 to clear DI0 count
260(bit1)
DI1 Count clear bit
Bool
Write 1 to clear DI1 count
260(bit2)
DI2 Count clear bit
Bool
Write 1 to clear DI2 count
260(bit3)
DI3 Count clear bit
Bool
Write 1 to clear DI3 count