Page 24 of 56
King Pigeon Hi-Tech. Co., Ltd.
Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
PT100/PT1000 Temperature Value:
It is the corresponding thermal resistance PT100 / 1000 channel converted
temperature value.
AO Output Test:
[AO1], [AO2] correspond to AO1 and AO2 channels. Adjust the DAC value of AO output by sliding
the slider. The output values of AO1 and AO2 cannot preset. In actual use, it is set by the host
computer, 12-bit accuracy, range is 0 ~ 4095, corresponding to the output voltage 0 ~ 10VDC, and
the maximum load is 1A.
Note:
After setting, please click "System Settings"-"Loading data" option to save the set parameters.
7.4 Network Settings
Got the IP address Auto:
Tick it stands for: the device automatically obtains the IP address in the LAN. Only when
the router in the LAN allows the dynamic allocation of IP addresses can be used.
User Specifies the IP Address:
Tick it stands for the user setup a fixed IP address for the module.
IP Address,Gateway,Netmask,Primary DNS,Secondary DNS:
Only can be set After choose ”User specifies the IP
address”.
Modbus TCP listening port:
1~65535, default is 502, listen TCP Client establish connection port, supports max 5
TCP Client connection.
Modbus over TCP Active Connection Settings:
Tick it stands for device will connect to the server automatically, or
will not connect.
Connection Mode:
Optional [Modbus RTU over TCP], [Modbus TCP], [MQTT] communication protocol.
Server 1/2 IP/Domain,Server 1/2 Port:
The device will connect to server 1 first, and connect to server 2 when the
connection fails.
Register Packets:
Registration packet sent by the device to the server when connecting to the server.