39 

Directory

 

Chapter 1  Safety ................................................................................................................................................... 40 

Chapter 2  Product introduction ............................................................................................................................. 41 

2.1 Nameplate Information ............................................................................................................................... 41 

2.2 VFD Model Rule ......................................................................................................................................... 41 

2.3 External dimension and weight .................................................................................................................. 42 

2.3.1 External dimension and weight ....................................................................................................... 42 

2.3.2 Operation panel and installation box size ....................................................................................... 44 

Chapter 3  Wiring Guide of VFD ............................................................................................................................ 45 

3.1 Wiring and Configuration of Main circuit terminal ...................................................................................... 45 

 ............................................................................. 45 

3.1.2 Wiring of VFD for Basic Operation .................................................................................................. 46 

3.2 Wiring and configuration of control circuit .................................................................................................. 46 

Chapter 4  Operation Instructions of Kinco VFD .................................................................................................... 49 

4.1 Using Operation Panel ............................................................................................................................... 49 

 .......................................................... 49 

4.1.2 Display status of operation panel .................................................................................................... 51 

4.1.3 Panel Operation............................................................................................................................... 51 

Chapter 5  Troubleshooting ................................................................................................................................... 52 

Chapter 6  List of Parameters ................................................................................................................................ 53

 

Summary of Contents for FV20 Series

Page 1: ...nstallation box size 44 Chapter 3 Wiring Guide of VFD 45 3 1 Wiring and Configuration of Main circuit terminal 45 45 3 1 2 Wiring of VFD for Basic Operation 46 3 2 Wiring and configuration of control...

Page 2: ...ause electric shock It is prohibited from changing internal parts or circuit nstall the drive in places where water pipes may leak onto it Don t allow screws washers and other metal foreign matters to...

Page 3: ...Information 2 2 VFD Model Rule FV20 4T 0075G 0110L A 037 Power Input Voltage Current freque Output Voltage Current freque Serial Number Model name CE certification 0 Standard model Others The second...

Page 4: ...2 Product introduction 42 2 3 External dimension and weight 2 3 1 External dimension and weight Fig 2 1FV20 4T 0185G 0220L and lower power VFD Fig 2 2FV20 4T 0220G 0300L FV20 4T 8000G Fig 2 5 FV20 4T...

Page 5: ...166 453 94 7 18 FV20 4T 0300G 0370L FV20 4T 0370G 0450L 320 535 224 220 512 88 5 10 31 FV20 4T 0450G 0550L FV20 4T 0550G 0750L 373 649 262 240 628 102 5 10 42 FV20 4T 0750G 0900L FV20 4T 0900G 1100L 4...

Page 6: ...Chapter 2 Product introduction 44 2 3 2 Operation panel and installation box size Fig 2 3 Installation box dimension Note When the operation panel is mounted the opening size of the tray is 65 130mm...

Page 7: ...n circuit terminal 3 Table 3 1 Description of main loop terminal Terminal name Function description L N Single phase 220VAC input terminal R S T 3 phase 380V AC input terminal DC bus positive and nega...

Page 8: ...circuit terminal function Table 3 2 Control circuit terminal function Sequence No Function 1 Analog input and output terminal RS232 and RSRS485 communication port Note It is recommended to use cables...

Page 9: ...nd GND Analog output AO1 Analog output 1 Providing analog voltage or current output they are selected by the jumper AO1 The default setting is output voltage refer to the function code A6 28 for detai...

Page 10: ...V power supply Providing 24V power for others Maximumoutputcurrent 200mA Common port PLC Common port of multi function input Common port of Multi function input Short cut with 24V in default Common po...

Page 11: ...r is in running state When the light is flashing it indicates that the inverter is in the self learning state When the light is off the inverter is in the stop state LOC REMOTE Panel operation termina...

Page 12: ...A Current unit HZ A V RPM V Voltage unit HZ A V RPM RPM Speed unit HZ A V RPM Percentage There are 8 keys on the operation panel and functions of each key are shown in Table 4 1 Table 4 1 Function li...

Page 13: ...n of A0 00 Edit state displays in 2 level menu they arefunction code group or function cod parameter value You can press ENTER to enter parameter displayed status In function parameter displayed statu...

Page 14: ...External device fault E016 EEPROM W R fault E017 VFD can not get communication with host E018 Power board drive board contactor damage causes contactor abnormal E019 Hall drive board abnormal causes c...

Page 15: ...be modified When you try to modify some parameters the system will check their modification property automatically to avoid mis modification Note 1 Parameter settings are expressed in decimal DEC and...

Page 16: ...indigital mode A0 11 A0 10 0 01Hz 50 00 O 0 30000 A0 04 Methods of inputting operating commands 0 Panel control 1 Terminal control 2 Communication control 1 1 O 0 2 A0 05 Set running direction 0 Forwa...

Page 17: ...g initial frequency at stop 0 00 60 00Hz 0 01Hz 0 00Hz O 0 6000 A1 07 Injection braking waiting time at stop 0 00 10 00s 0 01s 0 00s O 0 1000 A1 08 DC injection braking current at stop 0 0 0 1 0 0 O 0...

Page 18: ...Hz s 0 01 1 00 O 1 9999 A2 03 UP DN regulating control 0 Save reference frequency upon power outage 1 Not save reference frequency upon power outage 0 Hold reference frequency at stop 1 Clear referenc...

Page 19: ...10000 A3 05 Max reference of curve 2 A3 07 110 00 0 01 100 00 O 0 11000 A3 06 Actual value corresponding to the Max reference of curve 2 The same as A3 02 0 01 100 00 O 0 10000 A3 07 Min reference of...

Page 20: ...0000 A3 21 Characteristic selection of curve Characteristic choice of curve 1 0 set 0 Hz when frequency 0 Hz 1 symmetrical about origin 2 absolute value Characteristic choice of curve 2 0 set 0 Hz whe...

Page 21: ...ol mode 1 Torque control mode 1 0 X 0 1 A5 01 ASR1 P 0 1 200 0 0 1 2 0 O 1 2000 A5 02 ASR1 I 0 000 10 000s 0 001s 0 100s O 0 10000 A5 03 Switch frequency 1 0 0 A5 06 0 1 10 0 O 1 1000 A5 04 ASR2 P 0 1...

Page 22: ...3 wire operation control 6 External RESET signal input 7 External fault signal input 8 External interrupt signal input 9 Drive operation prohibit 10 External stop command 11 DC injection braking comma...

Page 23: ...que control switching terminal 42 Main frequency switch to digital setting 43 PLC pause 44 PLC prohibit 45 PLC stop memory clear 46 Swing input 47 Swing reset 48 49 Reserved 50 Motor 1 and motor 2 swi...

Page 24: ...negative when frequency less then center point 1 0 O 0 1 A6 12 Filter of pulse input 0 00 10 00s 0 01s 0 05 O 0 1000 A6 13 Input and negative logic Binary setting 0 Positive logic Terminal Xi is enab...

Page 25: ...d 1 0 O 0 65535 A6 18 Delay of relay R1 0 1 10 0s 0 1s 0 1 O 1 100 A6 19 Reserved 1 0 O 1 65355 A6 20 and negative logic Binary setting 0 Terminal is enabled if it is connected to Corresponding common...

Page 26: ...zero speed running 10 Terminal X1 Reserved 11 Terminal X2 Reserved 12 PLC running step complete signal 13 PLC running cycle complete signal 14 Limit of swing frequency upper lower limit 15 Drive read...

Page 27: ...ax output frequency 3 Preset frequency After Acc Dec 0 Max output frequency 4 Motor speed 0 Max speed 5 Output current 0 2 Iei 6 Output current 0 2 Iem 7 Output torque 0 3 Tem 8 Output power 0 2 Pe 9...

Page 28: ...0 65535 Group A7 PG Parameters A7 00 PG type 0 ABZ incremental type 1 UVW incremental type 2 Cosine type 3 Reserved 1 0 O 0 3 A7 01 Number of pulses per revolution of PG 1 10000 1 2048 O 1 10000 A7 02...

Page 29: ...deviation of speed fault masking overheat 0 Disable Stop when fault happen 1 Disable Continue operating when fault happen 2 Enable 1 00 X 0 22H A8 03 Motor overload protection mode selection 0 Disable...

Page 30: ...1A Determined by model X 1 9999 b0 11 Asynchronous motor 1 parameter auto tuning 0 disable 1 Stationary auto tuning Start auto tuning to a standstill motor 2 Rotating auto tuning 3 Reserved calculated...

Page 31: ...1 initial angle 0 FFFFH 1 0 X 0 FFFF b0 28 Synchronous motor 1 Z phase pulse initial angle 0 FFFFH 1 0 X 0 FFFF b0 29 Synchronous machine 1 overload protection coefficient 20 0 110 0 Set the action l...

Page 32: ...stop when instantaneous stop function selection 0 Disable 1 Enable Low voltage compensation Over modulation selection 0 Disable 1 Enable 1 001 X 0 111H b2 03 Over voltage point atstall 120 0 150 0 Udc...

Page 33: ...after stop in mode 1 1 0 X 0 2 Group b3 Communication parameter b3 00 Communication configuration Baud rate selection 0 4800BPS 1 9600BPS 2 19200BPS 3 38400BPS 4 115200BPS 5 125000BPS Data format 0 1...

Page 34: ...ction 1 Coast to stop 2 Stop in shortest time 3 Switch of input method of operating command 4 Switch forward reverse Save after power failure 5 Switch forward reverse Not save after power failure 1 0...

Page 35: ...n VFD stop not display in energy feedback mode BIT2 Analog close loop feedback Not display in energy feedback mode BIT3 Analog close loop setting Flick Not display in energy feedback mode BIT0 Bus vol...

Page 36: ...b5 05 Asynchronous motor 2 rated speed 0 60000RPM 1RPM 1440RPM X 0 60000 b5 06 Asynchronous motor 2 stator resistance R1 0 00 50 00 0 01 Determined by model X 0 5000 b5 07 Asynchronous motor 2 leakag...

Page 37: ...sistance 0 00 50 00 0 01 Determined by model X 0 5000 b5 22 Synchronous motor 2 straight shaft inductance 0 0 999 9mH 0 1mH Determined by model X 0 9999 b5 23 Synchronous motor 2 quadrature axis induc...

Page 38: ...eset frequency 3 Same as above 0 01Hz 15 00Hz O 0 30000 C0 03 Preset frequency 4 Same as above 0 01Hz 20 00Hz O 0 30000 C0 04 Preset frequency 5 Same as above 0 01Hz 25 00Hz O 0 30000 C0 05 Preset fre...

Page 39: ...fferential gain Kd 0 000 10 000 0 001 0 100 O 0 10000 C1 12 Sampling cycle T 0 01 50 00s 0 01s 0 50s O 1 5000 C1 13 Output filter 0 01 10 00s 0 01s 0 05 O 1 1000 C1 14 Error limit 0 0 20 0 Correspondi...

Page 40: ...eset close loop reference 14 10 00V 10 00V 0 01V 0 00V O 0 2000 C1 33 Preset close loop reference 15 10 00V 10 00V 0 01V 0 00V O 0 2000 C1 34 Close loop output reversal selection 0 The close loop outp...

Page 41: ...ting time 0 0 6500 0 0 1 20 0 O 0 65000 C2 07 Step 4setting Same as C2 01 1 000 O 0 323H C2 08 Step 4 operating time 0 0 6500 0 0 1 20 0 O 0 65000 C2 09 Step 5 setting Same as C2 01 1 000 O 0 323H C2...

Page 42: ...without memory LED Thousands Swing Frequency Status Power Down Storage 0 storage 1 not stored 1 0000 X 0 11111H C3 02 Swing frequency preset frequency 0 00Hz upper limit frequency 0 01Hz 0 00Hz O 0 3...

Page 43: ...Output terminals status 0 1FH 0 OFF 1 ON 1 0 0 1FH d0 16 AI1 input 10 00 10 00V 0 01V 0 00 0 2000 d0 17 AI2 input 10 00 10 00V 0 01V 0 00 0 2000 d0 18 Keyboard potentiometer input 10 00 10 00V 0 01V 0...

Page 44: ...ounter value 0 65535 1 0 0 65535 d0 41 d0 45 Reserved Group d1 Fault record d1 00 Fault record 1 0 No fault records 1 Hardware over current during acceleration 2 Hardware over current during decelerat...

Page 45: ...e unit failure E027 28 32 Reserved 33 VFD output is short circuit to earth E033 34 VFD running speed and encoder detected speed deviation exceeds allowed value E034 35 39 Reserved 40 Extension card an...

Page 46: ...Group d2 Product Identity Parameters d2 00 Serial number 0 FFFF 1 100 0 65535 d2 01 Software version number 0 65535 1 100 0 65535 d2 02 Custom made version number 0 65535 1 0 0 65535 d2 03 Load type s...

Page 47: ......