19
Example: Lock all the keys of the operation panel
Undrer stop parameter displaying status.
1 press MENU to enter A.00
2 Press
∧
to choose the function code b4.00
3 Press ENTER to entere the second level menu
4 Press
∧
to change the hundreds place from 0 to 1
5 Press ENTER to confirm
6 Press MENU to back the stop parameter displaying
status;
7 Press ENTER and hold, then press MENU, so the
key board is locked
Example 5: Unlock the keys of the operation panel
When the operation panel is locked, follow the follow
operations to unlock it:
Press the ENTER and hold , then press the
∨
three
times
Note:
Whatever setting is in b4.00, after the VFD power on,
the operation board is in unlock status.
5.2 Operation mode of VFD
In the follow-up sections, you may encounter the terms
describing the control, running and status of drive
many times. Please read this section carefully. It will
help you to understand and use the functions discussed
in the follow chapters correctly.
5.2.1 Control mode of VFD
It defines the physical channels by which drive
receives operating commands like START, STOP, JOG
and others, there are two channels:
1 Operation panel control: The drive is controlled by
RUN, STOP and M keys on the operation panel;
2 Terminal control: The drive is controlled by
terminals Xi
、
Xj and COM (2-wire mode), or by
terminal Xk (3-wire mode);
The control modes can be selected by function code
A0.04, multi-function input terminal (Function No.
15~17 are selected by A6.00~A6.04 )
Note:
Before you change the control mode, make sure that
the mode suitable for the application. Wrong selection
of control mode may cause damage to equipment or
human injury!
5.2.2 Operating Status
There are 3 operating status: stop, motor parameters
auto-tuning, and operating.
1.Stop status: After the drive is switched on and
initialized, if no operating command is accepted or the
stop command is executed, then the drive in stop
status.
2.Running status: The drive enters running status after
it receives the operating command.
3.Motor parameters auto-tuning status: If there is an
operating command after b0.11 is set to 1 or 2, the
drive enters motor parameters auto-tuning status, and
then enters stopping status after auto-tuning process
finishes.
5.2.3 Control mode and operation mode of Kinco
VFD
Control mode
CV100 VFD has three control methods, it is set by
A0.01:
0. Vector control without PG: it is vector control
without speed sensor, need not to install the PG, at the
same time it has very high control performance, it can
control the speed and torque of motor accurately. It has
the characteristics like low frequency with high torque
and steady speed with high accuracy. It is often used in
the applications that the V/F control mode can not
stisfy, but requires high robustness.
1. Reserved