6.1.
Set the analog inputs
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code
(see page 9).
➢
Press
OK
.
➢
Press Up key to go to the F 300 folder corresponding to the analog input of the channel 1 then press twice
OK.
“F300”
displays with the analog input below.
➢
Press
OK
.
The analog input flashes.
➢
Press the Up or Down key to select the required input signal :
•
4-20 mA
•
0-20 mA
•
0-10 V
•
0-5 V
•
0-2.5 V
➢
Press
OK.
The
“F300”
folder corresponds to the analog input of the channel 1.
For the channels 2 and 3 go to the following folders :
•
F310 for the channel 2
•
F320 for the channel 3
➢
Perform the same procedure as for the channel 1.
6.2.
Set the ranges of analogue outputs
This function allows to modify the ranges of the analogue inputs.
The values to enter depend on measurement unit selected and not of the measurement range of the
transmitter.
Ex : the minimum and maximum ranges on a CPE310-S pressure transmitter (0 to ±100 Pa) with a reading in mmH
2
O must
be configured on a measurement range from 0 to ±10 mmH2O. See conversion tables page 16.
The transmitter is powered on.
➢
Press
OK.
➢
Fill in the activation code
(see page 9).
➢
Press
OK.
➢
Press Up key to go to the F 301 folder corresponding to the low scale of the channel 1.
➢
Press
OK.
The first digit of the minimum range flashes.
➢
Enter with Up and Down keys the digit value or the negative sign of the value then press
OK.
The second digit flashes.
➢
Enter with Up and Down keys its value then press
OK
.
➢
Perform the same procedure for the following digits.
➢
Press
OK
when the last digit is configured.
F 301 flashes, the minimum range is configured.
➢
Press Up key then
OK
key to enter in the F 302 folder corresponding to the high scale of the channel 1.
The first digit of the maximum range flashes.
➢
Enter with Up and Down keys the figure of the digit or the negative sign of the value then press
OK.
The second digit flashes.
➢
Enter with Up and Down keys its value then press
OK.
➢
Perform the same procedure for the following digits.
15
F 300
: analog inputs management