KFP-CX3 Operation 

Manual 

P/N 501-419103-2-20 • ISS 19JUL21 

Summary of Contents for KFP-CX3

Page 1: ...KFP CX3 Operation Manual P N 501 419103 2 20 ISS 19JUL21...

Page 2: ...Directive 2014 30 EU 2012 19 EU WEEE Directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your...

Page 3: ...Advisory messages iii Introduction 1 Control panel overview 3 The user interface 3 Operator controls and indicators 4 Audible indicators 10 Control panel status indications 11 Control panel operation...

Page 4: ...less of whether Carrier has been advised of the possibility of such damages and regardless of whether any remedy fails of its essential purpose Installation in accordance with this manual applicable c...

Page 5: ...could result in injury or loss of life They tell you which actions to take or to avoid in order to prevent the injury or loss of life Caution Caution messages advise you of possible equipment damage...

Page 6: ...iv KFP CX3 Operation Manual...

Page 7: ...In this state fire sounders are activated immediately with a steady tone Fire routing if available is activated after any configured delay If an alarm is not reported in the second zone linked to the...

Page 8: ...ctivated Normally your system installer will have configured the extinguishing sounders to change to a continuous tone The extinguishing process cannot be stopped once it has started and extinguishing...

Page 9: ...tical Panel On LEDs 10 Door Fault Disabled LED 11 Networking Fault LED 12 Reserved for future use 13 Expansion I O Fault Disabled LED 14 General Disable button and LED 15 General Test button and LED 1...

Page 10: ...ablement or a test 2 Supply LED Green Indicates that the system is powered up 3 General Fault LED Yellow Indicates a fault The corresponding zone device or function fault LED also activates 4 General...

Page 11: ...uishing sounders are active sounding A flashing yellow LED indicates a wiring fault on the extinguishing sounders or if configured sounder outputs in expansion modules linked to the activation or rele...

Page 12: ...vating the actuator to ensure property protection A steady LED indicates a disablement Consult your system installer to determine whether your system has this option configured 11 Networking Fault LED...

Page 13: ...teady yellow LED indicates a disablement or test 17 Extinguishing Agent Flow LEDs Red Yellow Indicates the extinguishing agent flow status A steady red LED indicates that the extinguishing agent was r...

Page 14: ...lay countdown For more information see Stopping or restarting fire sounders on page 21 21 Numeric keypad and Enter button N A Used to enter the operator level password The Enter button is also used to...

Page 15: ...manual call point is active and the extinguishing process is paused A flashing yellow LED indicates an open or short circuit wiring fault A steady yellow LED indicates a disablement or test An MCP Hol...

Page 16: ...isablement or a test Consult your system installer to determine whether the Fire routing option is configured Audible indicators The control panel buzzer acts as an audible indicator to highlight syst...

Page 17: ...D Flashing while a delay countdown is in progress Steady if a delay is enabled Fire Sounders Start Stop LED Steady if fire sounders are active or will be activated shortly Flashing when a delay countd...

Page 18: ...detector activation Steady for MCP activation Fire Sounders Start Stop LED Steady as the fire sounders are activated immediately and any configured delay is bypassed Fire routing indications are shown...

Page 19: ...seconds before activating the actuator to release the extinguishing agent Flashing slowly if the actuator has been activated and the control panel is waiting for confirmation of the flow of the extin...

Page 20: ...f when the MCP Hold device is deactivated Extinguishing released The control panel is in this state when The actuator output to release the extinguishing agent has been activated and the agent flow co...

Page 21: ...ated by a steady General Disable LED and a steady yellow Extinguishing Sounders On LED Disabled fire sounders are indicated by a steady General Disable LED and a steady yellow Fire Sounders LED Disabl...

Page 22: ...low Released LED Extinguishing agent flow monitoring tests are indicated by a steady General Test LED and a steady yellow Extinguishing Agent Flow LED Extinguishing agent pressure monitoring tests are...

Page 23: ...y power is insufficient Flashing indicates that the mains power is insufficient and there is no battery power Supply Fault LED Steady indicates that there is no mains power Flashing indicates that the...

Page 24: ...rd security To enter the operator user level enter the password using the numeric keypad and then press Enter A long beep and a steady Reset LED indicate that the correct password was entered and that...

Page 25: ...by a manual call point overrides any configured delay and activates the fire sounders immediately Cancelling an active fire routing delay If a fire routing delay is enabled and active press the Fire...

Page 26: ...Test fire routing Disable or enable a zone Test a zone Disable or enable the extinguishing event Disable other extinguishing devices Test other extinguishing devices Set the manual only mode of opera...

Page 27: ...nted down The default disable time for the Fire Sounders Start Stop button is 1 minute The disable countdown begins when the control panel enters the fire alarm state and the configured fire sounder d...

Page 28: ...n or released state which activate continuously These outputs accept the stop and restart commands normally Disabling or enabling sounders To disable the fire sounders press the General Disable button...

Page 29: ...test without any configured delay To end the test press the General Test button and then press the corresponding sounder Fire Sounders Delay button again If there is an extinguishing preactivation act...

Page 30: ...ed delay for the duration of the test To end the test press the General Test button and then press the Fire Routing On button again If there is an extinguishing preactivation activation release or fir...

Page 31: ...arm event as configured Note The control panel buzzer and sounders may be configured not to sound when an alarm is activated in a zone being tested Disabling or enabling the extinguishing event Note W...

Page 32: ...ow monitoring Extinguishing Agent Flow yellow Extinguishing release optical warning panel sign Optical Panel On yellow Start extinguishing manual call points MCP Start yellow Hold extinguishing manual...

Page 33: ...t A steady Released LED indicates that the output is activated Extinguishing release optical warning panel or sign Optical Panel On yellow The optical panel output will be 3 seconds on 5 seconds off f...

Page 34: ...he system This inspection must test at least one device per zone and verify that the control panel responds to all fault and alarm events The control panel power supply and battery voltage should be c...

Page 35: ...54 2 clause 7 8 and should not be used for fire alarm devices 2 Requires installation of optional 2010 1 SB expansion board not supplied Table 7 EN 12094 1 optional requirements Option Description 4...

Page 36: ...iresecurityproducts com Certification Certification body 0370 Manufacturer Carrier Manufacturing Poland Sp lka Z o o Ul Kolejowa 24 39 100 Ropczyce Poland Authorized EU manufacturing representative Ca...