6.3.
Parallel Alarm Conditions and Connection Test
Setup
Conditions
Symptoms
Diagnosis
Action to
Rectify
Notes
KiloVault®
HAB™ V4
unit
s
connected in
parallel.
None of the
KiloVault®
HAB™ V4 unit
s
output power.
All KiloVault®
HAB™ V4
LCD
screens are lit.
All KiloVault®
HAB™ V4
RUN
LEDs are OFF.
All Alarm LEDs
flash 0.5s on,
0.5s off.
Leader ID
Communicati
on address
fault
protection.
No KiloVault®
HAB™ V4
unit
s in the
bank have
been set as
the Leader.
Set the
address DIP
switch of
one
KiloVault®
HAB™ V4
to
(1,0,0,0) or
(ON, OFF,
OFF, OFF),
setting it as
the Leader
KiloVault®
HAB™ V4
KiloVault®
HAB™ V4
unit
s
connected in
parallel.
None of the
KiloVault®
HAB™ V4 unit
s
output power.
All KiloVault®
HAB™ V4
LCD
Screens are lit.
All KiloVault®
HAB™ V4
RUN
LEDs are OFF.
All Alarm LEDs
flash 0.5s on,
0.5s off.
Leader
Communicati
on ID Address
Repeated.
More than
one
KiloVault®
HAB™ V4
has
been set as
the Leader.
Set only one
KiloVault®
HAB™ V4
address to
1,0,0,0. All
others
should be
set as
followers.
After setting
the correct
address,
restart the
KiloVault®
HAB™ V4
using the
front panel
power
switch.