LED will flash five times, the KiloVault® HAB™ V4 control panel
will light up, indicating the KiloVault® HAB™ V4 is operating
and supplying power to the inverter. Repeat steps 6 - 8 for each
KiloVault® HAB™ V4.
10
Start the inverter.
4.6.2.
Disconnecting the KiloVault® HAB™ V4
Warning:
After powering down a V4 HAB, you
must
wait at least 30
seconds before turning it back on again. Failing to wait at least
30 seconds risks causing internal short circuit events and
causing damage to its internal resistors.
NEVER reverse the polarity (positive and negative) of your unit’s connections.
NEVER short circuit your KiloVault® HAB™ V4.
Step
Number
Step Description
1
If disconnecting more than one
KiloVault® HAB™ V4
, power
off the other units one-by-one
by pressing each unit’s power
button.
2
Set the disconnect switch on the side of the
KiloVault® HAB™
V4 to the OFF position.
3
Disconnect the power cables from the
KiloVault® HAB™ V4
to
the inverter (or to the DC bus if installing more than one
KiloVault® HAB™ V4
), making sure to use overcurrent
protection as required.
4
Disconnect the Modbus communication cable between the
Leader
KiloVault® HAB™ V4
and the Inverter (if available).
4.6.3.
RJ45 120 Ω Resistor Plug Resistor Plug Installation
A clear RJ45 120 Ω Resistor Plug resistor plug is enclosed in each
KiloVault®
HAB™ V4
unit. Plug one end into the first and last units in the string as
shown.