4.6.1.
Connecting the KiloVault® HAB™ V4
Step
Description
1
Set the KiloVault® HAB™ V4 address using the address DIP
switch (refer to 4.6.7 Setting the KiloVault® HAB™ V4
2
If you are installing multiple KiloVault® HAB™ V4 units, connect
the RJ45 120 Ω Resistor Plug COM cables between the
KiloVault® HAB™ V4 units (refer to Section 4.6.3 RJ45 120 Ω
Resistor Plug Resistor Plug Installation and 4.6.4 Single Inverter
Simplified Wiring Diagram). This leaves an empty port on either
end of the string to install the clear resistor plug to terminate
the COM loop.
Note:
If a longer cable is needed, it can be replaced with any
RJ45 120 Ω Resistor Plug 6-position, 4-conductor, male
connectors both ends. Straight through. Maximum length, 10
feet.
3
Please contact KiloVault® for a list of supported inverters.
Connect the Modbus communication cable between the
Leader KiloVault® HAB™ V4 and the inverter.
4
Connect the power cables from the KiloVault® HAB™ V4 to the
inverter (or to the DC bus if installing more than one KiloVault®
HAB™ V4), making sure to use overcurrent protection as
required. Torque the terminals in the KiloVault® HAB™ V4
connection block to 5.65Nm or 4.17ft-lb or 50in-lbs
Note:
The KiloVault® HAB™ V4 battery connection block will
only accept 1/0 cables; do not attempt to use any other cables.
5
Close (switch to “On”) the Inverter main DC Breaker.
6
Close (switch to “On”) the battery breaker on the side of the
KiloVault® HAB™ V4
7
Press the KiloVault® HAB™ V4 power button at least three
seconds, until the “RUN” LED flashes five times.
8
Wait five seconds for the KiloVault® HAB™ V4 units pre-charge
function to complete.
9
If installing more than one KiloVault® HAB™ V4, start the other
units one-by-one by pressing the power button on the front of
the KiloVault® HAB™ V4 for at least three seconds. The "Run"