Operation instructions: Control head 5630xxx010-000
ASi-Bus ES/ABSL
16
16. Technical data
17. Fault clearance
Bus-system:
-
Control of valve position
Principle of effectiveness:
-
1 - 62 AB-Slave
Function of evaluation:
-
-10°C to +50°C
Range of address:
-
II (Control head with cap transparent)
I (Control head with cap stainless steel)
Operating temperature:
-
IP 67 (Control head with cap transparent)
IP 65 (Control head with cap stainless steel)
Appliance classes:
according to DIN EN61140 (VDE 0140-1)
-
22 - 30V DC
International protection rating:
according to DIN EN60529
80 mA
Distribution voltage:
-
Control of valve position
max. current consumption:
-
1 - 62 AB-Slave
Cable connection - control head:
-
Plug (14A); compression gland for daisy chain ASi (14B); Socket plug (14C)
Positioning sensor:
-
2 Hall-effect Sensors
Control air pressure:
-
2,5 - 8,0 bar
Air quantity passed:
-
140l/min. (6bar)
Weight:
-
0,5 kg
electr. magn. compatibility:
-
Test report FS/57.00/1147.9903
Display at site:
-
Mechanical valve indication and by LED. LED-Bus display
Quality of control air:
-
ISO 8573-1 : 2001 quality class 3
Material:
• Housing:
-
ABS - 6F
• Cap:
-
Standard:
ABS-transparent
Optional:
1.4301-(stainless steel)
• Seal:
-
EPDM; NBR; Viton®
FAULT
POSSIBLE REASONS
MEASURES
• Valve does not open
• External compressed air supply is not connected suffi-
ciently or not connected at all
• Make sure that the operating pressure required by the
valve fits closely at the external compressed air supply.
(for that purpose please apply the pressure instructions
of the valve producer)
• Compressed air supply between control head and valve
is interrupted or not connected
• Check air control lines
• Magnetic valve defect.
• exchange magnetic valve
• Electronic trigger is interrupted
• Check the triggers of the magnetic valves
• Valve does not close
• Magnetic valves are defect or the electronic or pneu-
matic trigger is disturbed
• Check the triggers of the magnetic valves
• This is caused by the valve
e.g. foreign particles between the sealing surfaces, drive
defect, etc.
• Switch valve manually in order to check the valve func-
tion
Clean valve housing