A
Page 11 / 16
Datasheet 2.50-40.151-11-EN
SBM51/11
Product Description
Issue 2014-11-19
Points Lists
Phase menu L1
DDC3000: M090 SBM51 Gateway
DDC4000: CD_SB51
NOTE
Due to rounding errors caused by scaling, the values of the parameters 2212, 2251, 2215 and 2252
in the DCC may differ from the display on the device (last digit).
Parameter
name
Parameter plain text Parameters provided
Operating mode L1
Unit
2209
External building com-
plex malfunction
Participant is logged in
2210
Analog actual value 1 Delta voltage U12
V
2211
Analog actual value 2 Phase voltage U1
V
2212
Analog actual value 3 Total energy incoming high rate
(k) Wh
2251
Analog actual value 4 Total energy incoming low rate
(k) Wh
2215
Analog actual value 5 Total energy outgoing high rate
(k) Wh
2252
Analog actual value 6 Total energy outgoing low rate
(k) Wh
2253
Analog actual value 7 Phase current I1
A
2254
Analog actual value 8 Effective power P1
(k) W
2255
Analog actual value 9 Apparent power S1
(k) VAr
2256
Analog actual value 10 Idle power Q1
(k) VA
2257
Analog actual value 11 Power factor cos
φ
2225
Digital actual value 3
0 – high rate / 1 – low rate
2217
Operating mode
Device present - 'Automatic'
Device not found - invalid