A
Page 18 / 24
Product Description
RBW322-FTL
Datasheet 1.10-60.015-01-EN
Issue 2016-05-16 ab V2.60
Service level
To activate the service level, proceed as follows:
■
Using an access code
■
Using a magnet
■
Pressing the set button briefly
Using an access code
►
Press the knob for 3 s.
►
Use the knob to select the “Service level” function
SR
.
►
Press the knob.
►
Enter the 4-digit access code 4321.
Each digit is entered individually and the entry is confirmed by pressing
the push-and-rotary knob.
If the access code was entered incorrectly, the display
ER
appears.
The room control module changes to the service level.
Using a magnet
►
Briefly press the magnet against the upper right-hand side
of the device (see figure).
The room control module changes to the service level.
The following functions are available on the service level:
■
Registration Function
■
Delete Function
■
Status display for taught-in radio partners
■
Valve position for service purposes
■
Restore default settings
■
Software version display
►
The push-and-rotary knob is used to select the individual functions of the service level.
If you do not take any other actions, the display will return to the initial display after 10 seconds.
Registration Function
1