Datasheet 2.50-40.132-01-EN

FBG132-FTL EnOcean System Gateway

Product Description

Issue 2013-08-13

CAN bus installation notes

Lines for the mains supply and fieldbus are to be laid together in one shielded cable, cable type at 
least 0.8 mm in diameter, with the wires twisted together in pairs. Here, one stranded pair of wires is 
to be used for the mains supply and the other for the fieldbus. 
At the end of the fieldbus (furthest point from the DDC controller, max. 2000 m), the two connection 
lines must be fitted with a terminating resistor of about 180 ohm (terminating resistor is included with 
the DDC controller).

Mounting

Removal

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

Summary of Contents for FBG132-FTL

Page 1: ...uct Description FBG132 FTL EnOcean System Gateway Application EnOcean system gateway for direct integration of up to 32 radio partners into the DDC4000 automation system for building automation and co...

Page 2: ...er or operator to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are f...

Page 3: ...faces EnOcean radio interface Radiogram EnOcean radiogram bidirectional Frequency 868 3 MHz Range approx 30 m in buildings depending on building structure Duty cycle 1 Bus connection Fieldbus max 2000...

Page 4: ...es F6 02 01 Light and Blind Control Application Style 1 LT10x FtL A5 20 01 Battery Powered Actuator MD10 FTL MD15 FTL 1 D5 00 01 Single Input Contact MK10 FtL MSC Manufacturer Specific Communication R...

Page 5: ...an System Gateway Product Description Issue 2013 08 13 EEP MSC radio communication mode FBG132 FTL with radio partners in EEP mode FBG132 FTL with radio partners in MSC mode MD15 FTL MK10 FTL FBG132 F...

Page 6: ...anges which can be reached Building materials and screening elements e g suspended ceiling elements installation shafts fire doors etc must be taken into consideration during planning NOTICE Elevated...

Page 7: ...at least 0 8 mm in diameter with the wires twisted together in pairs Here one stranded pair of wires is to be used for the mains supply and the other for the fieldbus At the end of the fieldbus furth...

Page 8: ...red LED are located under the housing next to the rotary switches Green LED 1 Red LED 2 Meaning Cause Off Off Module not in operation No operating voltage or operating voltage too low On On Module in...

Page 9: ...information in the PS4000 manual NOTE A button cannot be used for teaching in on the FBG132 FTL The radio ID of the radio partner is entered into the configuration parameters in the PS4000 planning sy...

Page 10: ...A Page 10 10 Product Description FBG132 FTL EnOcean System Gateway Datasheet 2 50 40 132 01 EN Issue 2013 08 13...

Reviews: