Kidde V-PHS Installation Sheet Download Page 2

 

2 / 2 

 

P/N 3101071-EN • REV 05 • ISS 24FEB16 

5.  Pull off the optical block chamber. 

6.  Blow off the optical block base in the detector body using clean 

compressed air. 

7.  Snap a new optical block chamber in place. Make sure you line up 

the two arrows on the block chamber with the snaps on the optical 
block base. 

8.  Connect the detector cap to the detector body by rotating the cap 

clockwise until it snaps into a locked position. 

9.  Install the detector onto the base. 

Note: 

To verify the effectiveness of the cleaning, recalibrate the 

device and run a device maintenance report. Refer to the technical 
reference manual. 

10.  Test the detector and verify sensitivity. 

Figure 2: Detector disassembly 

 

(1)  Slot to insert screwdriver 
(2)  Optical block chamber 
(3)  Optical block base 

(4) Detector body 
(5) Detector cap 

Testing 

NFPA 72 and CAN/ULC-S537 require a calibrated sensitivity test upon 
installation and following any modifications or additions to the system. 
The detector can perform this test and generate a system sensitivity 
report. 

Note: 

Both the smoke element and heat element of the detector must 

be tested. 

To test the detector: 

1.  Before initial testing, remove the dust cover from the detector and 

notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

2.  Test the detector’s smoke element using Smoke! In A Can (model 

SM-200) canned smoke. Carefully follow directions on the can to 
avoid damage to the detector. 

3.  Test the detector’s heat element using a heat gun while 

maintaining a six-inch minimum. Use caution as excess heat can 
damage the detector and detector housing. 

Specifications 

 
Communication line voltage 

20 V peak-to-peak max. 

Current 
 Normal 
 Alarm 

 
45 µA 
45 µA 

Smoke sensitivity range 
 UL 
 ULC 

 
0.67 to 3.66 %/ft. obscuration 
0.87 to 3.70 %/ft. obscuration 

UL/ULC fixed-temp alarm rating 

135°F (57°C) 

Environmental compensation 

Automatic 

Distance from ceiling (wall 
mounted) 

305 mm (12 po.) max. 

Compatible bases 
 Standard 
 Relay 
 Isolator 
 Audible 

 
B4U, B4U-LP 
RB4U 
IB4U 
SB4U, SB4U-LF 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Storage temperature 

4 to 140°F (

20 to 60°C) 

Regulatory information 

 
North American 
standards 

Meets: CAN/ULC-S529, CAN/ULC-S530, UL 268, 
UL 521 
Follow: CAN/ULC-S524, CAN/ULC-S537, 

National Building Code of Canada

National Fire 

Code of Canada

, and NFPA 72 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

Industry Canada 
compliance 

This Class A digital apparatus complies with 
Canadian ICES-003. 

 

Contact information 

For contact information, see www.kiddelifesafety.com. 

© 2016 Walter Kidde Portable Equipment, Inc.  
All rights reserved. 

(1)

(2)

(5)

XX

XX

XX

XX

(3)

(4)

Reviews: