background image

© 2021 Carrier 

1 / 3 

P/N 3102654-EN • REV 001 • ISS 12JAN21 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SA-USB Interface Card 

Installation Sheet 

 

Description  

The SA-USB Interface Card provides a USB connection to a supported 

printer or a connection to a PC. The card can be used for connecting a 

printer to the control panel to print system events. The card can also 

be used for PC communications, including the configuration utility (CU) 

and Firmware update utility (FUU).   
The default printer baud rate is 9600.   

SA-USB connectors and LEDs  

Refer to Figure 1 and Table 1 for a description of the SA-USB 

components. 

Figure 1: SA-USB LEDs and connectors 

 

Table 1: SA-USB connectors and LEDs 
Item  Label  Description 

(1) 

J4 

USB 2.0, Type B device port: Used as a temporary 

connection to a PC. 

(2) 

JP1 

Programming jumper: Shown in the not installed 

position. When installed over both pins, the jumper is 

used during programming the SA-USB to update 

firmware. This can 

only 

be accomplished with 

assistance from Technical Support.  

(3) 

J3 

USB 2.0, Type A host port: Used to connect supported 

printers. 

(4) 

J1 

Used to connect the SA-USB to the panel electronics 

board.  

(5) 

DS2 

TXD LED: Used to indicate all communications to the 

panel for both the printer and all PC applications. 

(6) 

DS1 

RXD LED: Used to indicate all communications from 

the panel for both the printer and all PC applications. 

(7) 

DS4 

TRBL LED: Used to indicate when it detects any 

printer trouble, such as off-line, out of paper, or the 

printer disconnected.  

Note: 

The panel will only display a printer trouble if the 

mode is set to supervised. 

 

LED operation  

Table 2: LED operation 
LED 

Operation 

DS1 

On steady. Flashes when the SA-USB is receiving data from 

the printer or PC applications. 

DS2 

On steady. Flashes when the SA-USB is transmitting data to 

the printer or PC applications.  

DS4 

On steady when a trouble exists between the SA-USB and the 

attached printer. 

Installation 

Install and wire this device in accordance with applicable national and 

local codes, ordinances, and regulations. 

Caution: 

Equipment damage hazard. This product is sensitive to 

electrostatic discharge (ESD). To avoid damage, follow accepted ESD 

handling procedures.   

Note: 

The SA-USB is installed in the same location as the SA-232, 

therefore the SA-232 card must be removed prior to installing the  

SA-USB card.  

To install the SA-USB: 

1.  Power down the panel and disconnect the batteries. 
2.  If installed, remove the SA-232 card from the panel. Refer to 

SA-

232 RS-232 Interface Card Installation Sheet

, P/N 3101095 for 

details. 

3.  Locate the SA-USB card location on the plastic assembly behind 

the main circuit board and connector J3 on the main circuit board 

(at the top-left of the main board). 

4.  Attach the SA-USB to the plastic assembly using two #6 plastite 

screws as shown in Figure 2. 

5.  Connect one end of the ribbon cable (P/N 7140187) to connector 

J1 on the SA-USB card and the other end to connector J3 on the 

main circuit board as shown in Figure 2. 

6.  Connect the applicable USB cable to the SA-USB. See “Wiring.” 

firealarmresources.com

Reviews: