background image

Evidence of conditions such as exposure to fire or heat, thread damage, 
thread wear, corrosion, cylinder repairs or physical damage as detailed 
within NFPA-10 require the extinguisher cylinder to be removed from 
service and proper disposal at the owner’s direction.

Hydrostatic testing should only be performed by those persons trained 
in the appropriate testing procedures/safeguards and having the proper 
testing equipment, facilities and information.

Some Kidde hydrostatic test recommendations:

•  Extinguisher cylinders should be replaced any time the pressure vessel  
  has been weakened due to corrosion, cuts, dents, digs, etc.
•  That only water be used as the test medium and that the extinguisher  
  then be flushed clean, dried and visually re-examined after testing.
•  The discharge valve assembly should be removed prior to hydrostatic  
  testing of the cylinder. (Refer to Note in Step 5 of Recharge  

 

  instructions.)
•  The agent cylinder hydrostatic test marking method should only    
  utilize the proper type of record labels per NFPA-10 requirements.
•  Never stamp or etch any markings onto the cylinder.
•  Any time a fire extinguisher is known to have contained agents,    
  additives or mediums other than that specified on the nameplate, it  
  should be removed from service and properly disposed at the owner’s  
  direction.
•  No repairs to the cylinder are permitted. If such cylinder repairs are  
  observed, the extinguisher should be removed from service and    
  properly disposed at the owner’s direction.

Hydrostatic Re-Test Data:

Component Description 

Periodic Test Interval 

Test Pressure

Agent cylinders 

12 year   

 

 

585 PSI

11

Summary of Contents for Pro 10 RM-4

Page 1: ...2 lb 20 lb Agent Capacity Service Manual Stored Pressure Dry Chemical Hand Portable Fire Extinguishers Pro Line...

Page 2: ...re to follow the instructions contained herein may result in property damage and or personal injury Important Notice Important Notice Any time an unusual extinguisher discrepancy is noticed or the spe...

Page 3: ...eference procedures in CGA pamphlets C 1 C 2 and C 6 NFPA Government Printing Office Compressed Gas Association 1 Batterymarch Park P O Box 371954 1235 Jefferson Davis HWY Quincy MA 02269 Pittsburgh P...

Page 4: ...her carrying handle transport the unit to a safe position upwind of the fire 4 Remove the hose nozzle from the retention clip if equipped and while keeping the extinguisher in a vertical position aim...

Page 5: ...nitially placed into service and there after at approximately 30 day intervals When circumstances require more frequent intervals may be necessary Any time an inspection reveals a discrepancy maintena...

Page 6: ...isher is installed in its proper location and that it is readily accessible Most Kidde dry chemical extinguisher models are approved for temperature ranges between 40 F to 120 F 2 Remove extinguisher...

Page 7: ...ul not to accidentally discharge the extinguisher pull and remove the ring pin breaking the visual inspection seal to ensure the ring pin functions freely and is not bent damaged or corroded Re instal...

Page 8: ...miliar with the contents of this manual to recognize any equipment conditions or discrepancies that might prohibit the recharge of the extinguisher or direct further equipment maintenance or repair 1...

Page 9: ...discoloration or contaminants If necessary remove extinguisher from service and replace 10 Add the proper type and quantity of Kidde dry chemical agent specified on the extinguisher nameplate recharg...

Page 10: ...sher surfaces Note Prior to placing recharged dry chemical extinguishers back into fire protection service Kidde recommends the extinguisher pressure gauge reading be re verified a minimum of 24 hours...

Page 11: ...hen be flushed clean dried and visually re examined after testing The discharge valve assembly should be removed prior to hydrostatic testing of the cylinder Refer to Note in Step 5 of Recharge instru...

Page 12: ...eads outside green area Check ambient temperature correlation De pressurize and recharge or replace Pressure gauge damaged De pressurize and replace Gauge operating pressure differs from label De pres...

Page 13: ...Pro 2 75 RM 5 Pro 2 75 RM 5 Pro 4 TCM 4 Pro 4 TCM 4 Pro 4 TCM 4 Part Number 466227 466227 466228 466228 466228 466288 1 320337 320337 320338 440310 2 21005736 21005736 21005736 21005737 3 21005739 210...

Page 14: ...10 Hose strap Model Pro 10 TCM 5 Pro 10 TCM 6 Pro 20 RM Pro 20 RM Pro 20 RM 4 Pro 20 RM Pro 20 RM Pro 20 RM 5 Part Number 466204 466204 46620 46620 466207 7 7 466207 1 440329 440329 440127 440127 2 21...

Page 15: ...ing 4 O ring kit includes valve o ring syphon tube o ring stem assembly stem assembly spring 5 Wall hanger 6 Retention bracket 7 Pull pin 8 Pressure gauge 9 Hanger loop and screw 10 Hose strap Model P...

Page 16: ...Kidde Residential and Commercial 1394 South Third Street Mebane NC 27302 9711 Phone 1 800 880 6788 Manual P N 300290 Copyright Kidde 2005...

Reviews:

Related manuals for Pro 10 RM-4