background image

 

© 2017 United Technologies Corporation 

1 / 2 

P/N 3102533-

EN • REV 001 • ISS 15AUG17 

 

KIR-PHD Intelligent 
Multisensor Photo-Heat 
Detector Installation Sheet 

 

Description 

The model KIR-PHD Intelligent Multisensor Photo-Heat Detector is an 
intelligent device that contains a photoelectric smoke sensor and a 
rate-of-rise heat sensor with a fixed temperature setting. The detector 
analyzes the data from both sensing devices and determines whether 
an alarm should be initiated. Can be operated as a single detector 
using smoke or heat to initiate an alarm. 

LED indicator. 

The LED indicator (see Figure 2) displays the following 

states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Installation 

Notes

 

• 

This detector does not operate without electrical power. As fires 
frequently cause power interruption, discuss further safeguards 
with the local fire protection specialist. 

• 

This detector does not sense fires in areas where smoke or heat 
cannot reach the detector. Smoke or heat from fires in walls, roofs, 
or on the opposite side of closed doors may not reach the detector. 

• 

Photoelectric detectors have a wide range of sensing capabilities, 
and are best suited for detecting slow, smoldering fires. The heat 
sensor in this device provides a source of supplemental 
information. The heat sensor by itself does not provide life safety 
protection. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

In Canada, install according to the CAN/ULC-S524 

Standard for 

the Installation of Fire Alarm Systems,

 the CSA

 

C22.1 

Canadian 

Electrical Code

, and the local authority having jurisdiction. 

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. The Kidde Intelligent devices can 
perform this test at the panel which can then generate a system 
sensitivity report. 

To install the device: 

1.  Install and wire the base, as described on the installation sheet 

supplied with the base. 

2.  Set the detector address.  Refer to the panel technical reference 

manual for a list of valid addresses.  Use a screwdriver to adjust 
the two rotary switches on the back of the detector.   
(See Figure 1)  Set the left rotary switch (0 through 12) for the 10s 
and 100s digit and the right rotary switch for the 0 through 9 digit. 

3. 

Attach the detector to the base by rotating the detector clockwise 
until it snaps into the locked position. 

Figure 1: Setting detector address (address 52 shown) 

 

 

 

 

 
 
(1) Insert a screwdriver here to set the address 

Figure 2: KIR-PHD features 

2

 

 
(1)  Self-locking tab 
(2)  LED indicator 

 

 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Test each sensor in the detector.  

Caution: 

Heat damage. Excessive heat may damage the detector 

outer cover. Do not apply excessive heat when using a hair dryer. 
When using a Testifire detector tester, you must install a Testifire 
Adapter Assembly. 

Make sure the Testifire Adapter Assembly (model 
SIGA2-TSTSPACER) is installed in the Testifire detector tester before 
testing. Refer to the 

Testifire Adapter Assembly Installation Sheet 

(P/N 

3101942-ML) for further details. 

0

2

3

4

5

6

8

9

0

1

2

3

4

5 6 7 8

9

0

1

11

1

1

2

TENS

ONES

(1)

Reviews: