P/N P-047550-1819-EN • REV 005 • ISS 22MAR17 

Figure 2: Wiring diagram (rear view) 

 

(1)  Factory connections — do not alter 
(2)  Green LED (normal) 
(3)  Red LED (alarm/active) 
(4)  Signaling line circuit (SLC) from previous device 
(5)  Signaling line circuit (SLC) to next device 
(6)  All wiring is power-limited and supervised. Refer to the Signature 

Controller Module installation sheet for wiring specifications. 

 

Specifications 

 

Voltage 

15.20 to 19.95 VDC 

Current 
 Standby 
 Activated 

 
250 µA 
400 µA 

Wire size 

12 to 18 AWG (1.0 to 4.0 mm²). 

16 and 18 AWG (1.0 and 1.5 mm²) are 
preferred 

Operating mechanism 

Double action, pull lever 

Construction 

High impact plastic with steel backplate 

Compatible electrical 
boxes 

North American 2-1/2 in. (64 mm) deep 
single-gang box 

Standard 4 in. square box 1-1/2 in. (38 mm) 
deep box with single-gang cover 

276B-RSB red surface mount box 

Operating environment
 Temperature
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Replacement glass 
rods 

P/N 276-GLR (pkg. 20 rods) 

 

Regulatory information 

 

ADA 

This device meets the ADA requirements for 
manual pull stations. 

ULC requirements 

To meet CAN/ULC-S527 ESD requirements, the 
device must be mounted in a grounded metal 
backbox. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

 