P/N 3102667-EN • REV 002 • ISS 31AUG20
3 / 4
Figure 6: Wiring
(1) Speaker circuit in (shields, if used, must be continuous and free
from earth ground except at the signal source)
(2) Strobe circuit in (signal polarity shown in the active condition)
(3) Speaker circuit out
(4) Strobe circuit out
(5) Shorting clip
Note:
To maintain circuit continuity,
do not remove the shorting clip
(Figure 6, item 5) until you are ready to install the notification
appliance.
Figure 7: Removing and replacing the appliance
Maintenance and testing
Caution:
Equipment damage hazard. To maintain the required agency
listings, do not change factory-applied finishes.
This unit is not serviceable or repairable. If the unit fails to operate,
contact the supplier for a replacement.
Perform a visual and operational inspection in accordance with
applicable codes and standards or as directed by the local authority
having jurisdiction.
Input wiring test points are available on the front of the appliance when
the cover is removed. The test points let you easily spot check the field
circuit wiring without the need to remove the appliance from the wall.
Figure 8: Strobe circuit test points
Note:
Marking indicates signal polarity when the circuit is active.
Figure 9: Speaker circuit test points
Specifications
Operating voltage
Strobe
Speaker
16 to 33 VDC, 16 to 33 VFWR
25 VRMS, 70 VRMS (field selectable)
Operating current
16 to 33 VDC
16 to 33 VFWR
28 mA
36 mA
Supervisory voltage
30 V max.
Sound output
Speaker response
400 to 4,000 Hz
Resonant frequency
520 Hz
Strobe flash rate
1 fps (flash per second) approx.
Light output
15, 30, 75, or 110 cd
Light distribution
Synchronization
20
Ω max. between any two devices.
To determine allowed wire resistance, refer
to these specifications, and the specifications
for the synchronized signal source.
Dimensions
Center offset
−1.70 in (−4.32 cm)
Compatible electrical
boxes [1]
2-gang, 4-inch square, G4RSB, G4WSB
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Screw torque
Mounting screws
Terminal screws
10 lbf-in (1.2 N-m) max.
12 lbf-in (1.4 N-m) max.
(2) –
+
(4)
(5)
–
+
(1)
–
+
(3)
–
+