TM204
24 of 56
Issue 1.1
6.1
Adding New Status Indicators/Ancillary Boards
When the system is powered, it will search for connected status indicators and/or ancillary boards
connected to Extinguishing modules.
If status indicators or ancillary boards are fitted and detected by the control panel, the LCD will display:
X = the number of faults
Press ENTER on the module to which the status indicators or ancillary boards are connected with the
ENABLE CONTROL keyswitch off and use the (+) button on the module to view the faults. If status
indicators and/or ancillary boards are detected the LCD will display:
X = the address of the status unit found
Or
X = the address of the ancillary board found
To accept the status indicators and/or ancillary boards found, turn the ENABLE CONTROL keyswitch on
and slide the WRITE ENABLE switch on the module to which the status indicators or ancillary boards
are connected gently to the left.
The LCD will then display:
X = the address of the status unit found
Or
X = the address of the ancillary board found
When the ENTER button is pressed on the module to which the status indicators or ancillary boards are
connected, the selected status indicator or ancillary board will be added to the system and the next unit
to be added will be displayed. Press the ENTER button on the extinguishing module until all of the units
have been accepted, then gently slide the WRITE ENABLE switch on the module to the right.
Once all of the status indicators and ancillary boards found by the extinguishing module have been
added, disconnection of any of them will be displayed as a fault on the extinguishing and detection
modules. If any status indicators are disconnected, a HOLD activated indication will also be displayed on
the extinguishing module and all ancillary boards or status indicators that remain connected.